ID-FLX Lite & Telecom Global Guide
125
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 1000 [min]
Default value
0
-
Step
1
Comm object
11837
Related applications
Description
Automatic engine stop in MAN mode or delayed engine stop in AUT mode. Start engine in MAN mode by
START button. Engine stops itself after Running Timer is over. Engine stays running when
= 0
Running timer
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 10000 [L]
Default value
200
-
Step
1
Comm object
11103
Related applications
Description
This setpoint is describing volume of fuel tank for counting fuel consumption depending on Fuel level drop.
FuelTankVolume
Setpoint group
Engine parameters
Related FW
2.5.0
Range [units]
0 .. 50 [%/h]
Default value
25
-
Step
1
Comm object
12373
Related applications
Description
This is setting protection against the fuel leakage or theft.
Function monitors the AIN3 Fuel level value in percentage scale without decimals. The alarm and history
record “Wrn FuelTheft” is activated when Fuel level change is faster than setpoint limit. Function is switched
off when Max Fuel Drop = 0 %/h.
The drop out limit on stopped engine is 5% to avoid unwanted Alarm activation due to AIN3: Fuel level
fluctuations.
Active alarm "Wrn FuelTheft" can be sent via SMS and displayed by WebSupervisor (if used).
Note:
Set 0 to disable Fuel Theft Protection function into MaxFuelDrop setpoint.
MaxFuelDrop
Summary of Contents for ID-Lite
Page 16: ...ID FLX Lite Telecom Global Guide 16 4 3 Terminal diagram and dimension...
Page 18: ...ID FLX Lite Telecom Global Guide 18 Example Default analog output curves...
Page 19: ...ID FLX Lite Telecom Global Guide 19 Example Wiring for Dacon gauges and IL NT AOUT8...
Page 41: ...ID FLX Lite Telecom Global Guide 41 5 2 Binary inputs and outputs...
Page 54: ...ID FLX Lite Telecom Global Guide 54 5 14 Display screens and pages structure...