ECON-4 1.4.0 Global Guide
70
Setpoint group
ActType 1,2,3,4
Related FW
1.4.0
Range [units]
0.0 – 100.0 [%]
Default value
100%
Force value
NO
Step
0.1 %
Comm object
11112
Related applications
ALL
Setpoint visibility
WinScope only
Description
Actuator Overload protection limit.
Act MaxCur
Setpoint group
ActType 1,2,3,4
Related FW
1.4.0
Range [units]
0.0 – 300.0 [s]
Default value
5 s
Force value
NO
Step
0.1 s
Comm object
11113
Related applications
ALL
Setpoint visibility
WinScope only
Description
Actuator Overload protection limit delay.
ActmaxCurDel
Setpoint group
ActType 1,2,3,4
Related FW
1.4.0
Range [units]
0.0 – 100.0 [%]
Default value
40%
Force value
NO
Step
0.1 %
Comm object
11114
Related applications
ALL
Setpoint visibility
WinScope only
Description
Reduced actuator current when overload protection was activated.
Act ReducedCur