Measuring device 3760XBI

© 2021 Comap. Tous droits réservés. Nous nous réservons le droit d’apporter des 

changements quant à la conception et quant aux spécifications techniques de nos produits.

Page 2 - 00012 - ENG - 2021-12

2. Configuration

Pre-recorded valve selection

Before starting to measure, please specify the valve

Select a pre-recorded valve

VALVE

Comap

750 AB  

DN 20

To use identical valves several times, just modify the setting.

PRESET

Max : 40

32.0

Min: 5

Enter the position indicated 

on the display of the valve

Measure by kv value

If the valve cannot be found, and the value of the kv is known, the kv value is needed. 

Proceed as previously to select in the valves list « Direct Kv »  then « 0 – 50000 »

Enter the Kv value

PRESET

Direct Kv

23.5

Min: 5

Enter the appropriate kv 

value

Entering value

Each value is entered digit by digit

ZERO

Deletes the last digit

>

Decreases the value of the digit (0-9 

and .)

Validates and creates a new digit

>

Increases the value of the digit (0-9 

and .)

PRESET

Next field (OK)

3. Changing the fluid

The fluid type is displayed on the left bottom of the screen

MENU

Fluid

Select the type, concentra-

tion and temperature

4. Connect

Resetting

This procedure should be done when restarting the device. Recommended before all measure.

ZERO

1. Connect the hoses to the valve:

 

Red: Valve upstream

 

Blue: Valve downstream

OK

OK

OK

OK

OK

<

<

<

<

<

<

<

<

<

<

Summary of Contents for 3760XBI

Page 1: ...rument MENU Display Menu or Back to previous menu level ZERO Reset or Delete cancel Cancel or Back to previous level OK Display pressure flow Kv date hour or validates the selection VALVE Valve selection or Previous page from the list PRESET Valve setting position or Next page from the list Reduces the value or Next field or Next element from the list Increases the value or Previous field or Previ...

Page 2: ... the value of the kv is known the kv value is needed Proceed as previously to select in the valves list Direct Kv then 0 50000 Enter the Kv value PRESET Direct Kv 23 5 Min 5 Enter the appropriate kv value Entering value Each value is entered digit by digit ZERO Deletes the last digit Decreases the value of the digit 0 9 and Validates and creates a new digit Increases the value of the digit 0 9 and...

Page 3: ...rding select the valve Give a name to the record see entering values Indicate the recording duration and the number of samples Start the recording The instrument automatically puts into sleep mode to save battery but keeps on recording Press to turn on the instrument Attention DO NOT FORCE THE EXTINCTION THIS MAY RESUME THE RECORDING 7 Valve in memory Most of the valves from the following manufact...

Page 4: ... 10 Maintenance Replace the hoses filters The filters for the flexible hoses ref 3760F should be replaced every 6 month to prevent dirt obstruction Instrument periodic maintenance and calibration The device should be periodically re calibrated every year Please return the device to your local Comap representative The information about the last calibration date can be found in the menu Options devi...

Reviews: