background image

16

Minimum Loop Volume — The preferred minimum loop
volume is equal to twice the water flow rate per ton. (For
example, the preferred water volume for 2.4 GPM/ton would
be 2 x 2.4 = 4.8 gallons in the loop per ton of cooling.) In order
to obtain leaving water temperature stability for comfort cool-
ing applications, a minimum of 3 gallons per ton is required on
all other unit sizes. For process cooling applications, where
high stability is critical, the loop volume should be increased to
6 to 10 gallons per ton of cooling.

In order to achieve this volume, it may be necessary to add a

water storage tank to the water loop. (The compression/
expansion tank on the 30RA hydronic package is NOT a
storage tank. If a storage tank is added to the system, it should
be properly vented so that the tank can be completely filled and
all air eliminated. Failure to do so could cause lack of pump
stability and poor system operation.)
NOTE: On systems with a high volume, check the section on
maximum loop volume. A different expansion tank may be
required on systems with very high loop volumes.

Any storage tank that is placed in the water loop should

have internal baffles to allow thorough mixing of the fluid. See
Fig 17.

A properly baffled storage tank is available from the factory

as an accessory. These tanks are designed to physically fit
beneath the corresponding 30RA unit, taking up the same
footprint.
 Available volumes are as follows:
•  30RA010-018          110 gallons
•  30RA022-030          152 gallons
•  30RA032-055          305 gallons
Maximum Loop Volume — Since the minimum size of the
expansion tank is dependent upon loop volume, units with the
integrated hydronic kit must not exceed the maximum loop
volume limits below (see Table 6). The limits are dependent on
the maximum and minimum temperatures of the water, the
maximum and minimum pressures seen by the expansion tank,
and the heat transfer fluid. Expansion tank and maximum loop
volume data is as follows.

30RA010-030

         30RA032-055

Volume gal

4.4

10.3

Acceptance Volume gal

3.2

10.3

1

2

3

4

6

5

30

20

10

5

2

1

1

2

3

4

5
6

Flow Rate (L/S)

Heat Exchanger Pressure Drop (KPa)

5

6

7

8

9

10

7

8

9

10

11

25

20

10

5

Flow Rate (L/S)

Heat Exchanger Pressure Drop (KPa)

LEGEND

Fig. 15A — Heat Exchanger Pressure Drop —

30RA010-030 (English)

1

30RA010

4

30RA022

2

30RA015

5

30RA025

3

30RA018

6

30RA030

LEGEND

Fig. 15B — Heat Exchanger Pressure Drop —

30RA010-030 (SI)

1

30RA010

4

30RA022

2

30RA015

5

30RA025

3

30RA018

6

30RA030

LEGEND

Fig. 16A — Heat Exchanger Pressure Drop —

30RA032-055 (English)

7

30RA032, 30RA035

10 —

30RA050

8

30RA040

11 —

30RA055

9

30RA042, 30RA045

LEGEND

Fig. 16B — Heat Exchanger Pressure Drop —

30RA032-055 (SI)

7

30RA032, 30RA035

10 —

30RA050

8

30RA040

11 —

30RA055

9

30RA042, 30RA045

Summary of Contents for AquaSnap 30RAN010-055

Page 1: ...ure and on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in han...

Page 2: ...8 018 110 146 203 194 653 018 117 161 218 215 711 022 174 237 198 186 795 022 187 268 215 211 881 025 181 241 204 198 824 025 194 272 221 224 911 030 193 268 210 207 878 030 208 308 224 241 981 035 37...

Page 3: ...i freeze in cooler to prevent freezing of residual water 4 At the beginning of the next cooling season refill cooler and add recommended inhibitor Fig 3 Unit Rigging Label Detail C Copper Finned Conde...

Page 4: ...sq ft 23 23 23 32 32 40 55 55 64 64 80 HYDRONIC MODULE Optional Pump s Strainer W Blowdown Valve Expansion Tank Pressure Gages Drain and Vent Plugs Flow Switch and Balance Valve Pump Single or Dual C...

Page 5: ...2 97 2 97 3 72 5 11 5 11 5 95 5 95 7 43 HYDRONIC MODULE Optional Pump s Strainer W Blowdown Valve Expansion Tank Pressure Gages Drain and Vent Plugs Flow Switch and Balance Valve Pump Single or Dual C...

Page 6: ...olid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side cl...

Page 7: ...id surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clea...

Page 8: ...surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to out side edge of hail guard top panel 3 Coil side clear...

Page 9: ...id surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clea...

Page 10: ...lid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side cle...

Page 11: ...d surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clear...

Page 12: ...hould follow sound engineer ing practice as well as applicable local and industry standards Improperly designed or installed systems may cause unsatis factory operation and or system failure Consult a...

Page 13: ...l a temporary bypass around the chiller to avoid cir culating dirty water and particulates into the pump pack age and chiller during the flush Use a temporary circulat ing pump during the cleaning pro...

Page 14: ...pressure drop between the tank and the pump must be accounted for NOTE If the system requires a pre charge greater than 40 psig increase pressure as described below Expansion Tank Pre Charge To pre c...

Page 15: ...of the city water system should be consulted and followed to prevent contamination of the public water supply This is especially important when anti freeze is used in the system Set Water Flow Rate O...

Page 16: ...available from the factory as an accessory These tanks are designed to physically fit beneath the corresponding 30RA unit taking up the same footprint Available volumes are as follows 30RA010 018 110...

Page 17: ...where ambient tempera tures are expected to fall below 32 F Consult local water treat ment specialist on characteristics of the system water and add a recommended inhibitor to the chilled water 1 If t...

Page 18: ...agement Module Used for any of the following types of temperature reset demand limit and ice features 4 to 20 mA leaving fluid temperature reset requires field supplied 4 to 20 mA generator 4 to 20 mA...

Page 19: ...2 2 125 311 3 110 96 2 125 110 97 4 125 110 97 4 125 110 99 6 125 110 208 230 60 187 253 1 102 4 125 316 4 125 106 8 125 125 108 2 125 125 108 2 125 125 110 6 150 125 460 60 414 506 1 50 3 70 160 0 60...

Page 20: ...0 2 1 9 1 3 0 380 60 2 2 9 1 4 6 042 380 415 50 2 2 3 2 2 3 230 50 2 3 8 2 3 8 045 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 2 1 9 2 1 9 380 60 2 2 9 2 2 9 380 415 50 2 2 3 2...

Page 21: ...205 34 1 225 41 6 310 035 230 60 29 4 265 36 7 265 43 8 380 208 230 60 32 7 265 40 8 265 48 7 380 460 60 14 6 120 20 2 135 23 8 175 575 60 12 2 80 16 6 120 18 9 140 380 60 18 9 155 26 4 170 30 1 235...

Page 22: ...move the orange harness wire from TB5 1 and wire contacts in series as shown The contacts must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA 5 Terminals 11 and 13...

Page 23: ...nge harness wire from TB5 1 and wire contacts in series as shown The contacts must be rated for dry cir cuit application capable of handling a 24 vac load up to 50 mA 5 Terminals 11 and 13 of TB5 are...

Page 24: ...s 6 and 7 for details Do not use compressor to evacuate system REFRIGERANT CHARGE Refer to Tables 1A 1D Immediately ahead of filter drier in each circuit is a factory installed liquid line service val...

Page 25: ...PUMP UNITS 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA010 030 PRESSURE DROP SINGLE PUMP UNITS 30RA010 030 LEGEND 1 30RA010 3 30RA018 5 30RA025 7 30RA032 30RA035 9 30RA042 30RA045 11 30RA055 2 30R...

Page 26: ...DUAL PUMP UNITS SIZES 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA032 055 LEGEND 1 30RA010 3 30RA018 5 30RA025 7 30RA032 30RA035 9 30RA042 30RA045 11 30...

Page 27: ...Accessory Storage Tanks 1 ACCESSORY TANK FLOW RATE gpm PRESSURE DROP ft wg 30RA 900 010 30RA 900 001 009 100 0 10 0 1 0 0 1 10 100 1000 0 1 1 0 10 0 1 0 10 0 ACCESSORY TANK FLOW RATE L s PRESSURE DROP...

Page 28: ...scontinue or change at any time specifications or designs without notice and without incurring obligations PC 903 Catalog No 533 00045 Printed in U S A Form 30RA 12SI Pg 28 7 02 Replaces 30RA 1SI Book...

Reviews: