![Colombo Construction 54LL Owner'S Manual Download Page 4](http://html1.mh-extra.com/html/colombo-construction/54ll/54ll_owners-manual_2637585004.webp)
HOT SURFACE IGNITION PILOT LIGHT
54 - 68 LL and NL ELECTRONIC IGNITION FIREBOWL
TECHNICAL
QUICK VIEW
!
4
FOR OUTDOOR USE ONLY
Model: 54 - 68 LL and NL ELECTRONIC IGNITION FIREBOWL
OUTDOOR FIREPLACE
Type of Gas: Natural Gas (NG), Liquid Propane (LP)
ORIFICE SIZES:
NG Maximum BTU = 290,000 BTU @ 7” W.C. Inlet - 6” W.C. Manifold
LP Maximum BTU = 290,000 BTU @ 11” W.C. Inlet - 10” W.C. Manifold
INSTALLATION BY CERTIFIED GAS TECHNICIAN ONLY
MINIMUM CLEARANCE TO COMBUSTIBLES:
Top: 12ft (144”) - Sides: 2ft (24”)
INSTALLATION ON (OR OVER) NON-COMBUSTIBLE FLOORS ONLY.
TO LIGHT APPLIANCE:
NOTE: BEFORE OPERATING APPLIANCE ENSURE THE MANUAL GAS SHUTOFF VALVE IS OPEN.
1.
PRIOR TO TURNING APPLIANCE ON
- VISUALLY INSPECT APPLIANCE TO ENSURE DEBRIS SUCH AS LEAVES OR OTHER COMBUSTIBLE MATERIAL
HAS NOT COLLECTED INSIDE THE APPLIANCE WHICH COULD BURN AND EMIT EMBERS ONCE THE APPLIANCE IS
TURNED ON.
- ENSURE ANY PERSON STANDING CLOSE TO THE APPLIANCE IS AWARE YOU WILL BE TURNING THE APPLIANCE
ON PRIOR TO ACTUALLY TURNING IT ON.
2.
TURN APPLIANCE ON BY TURNING ON THE ELECTRICAL DEVICE USED TO POWER THE APPLIANCE.
SEQUENCE OF OPERATION DURING IGNITION
- POWER IS APPLIED
- HOT SURFACE IGNITER (GLOW PLUG) BECOMES HOT AND PILOT GAS VALVE OPENS
- WITHIN 10 SECONDS OF POWER APPLICATION PILOT FLAME SHOULD BE VISIBLE (AT NIGHT ONLY)
- WITHIN 10 SECONDS OF PILOT FLAME IGNITION, BURNER ELEMENT SHOULD IGNITE
IF MAIN BURNER DOES NOT LIGHT, OR YOU SMELL OR HEAR GAS, IMMEDIATELY TURN PLAIN VIEW
GAS VALVE TO OFF POSITION.
TO PUT OUT APPLIANCE:
TURN APPLIANCE OFF BY TURNING OFF THE ELECTRICAL DEVICE USED TO POWER THE APPLIANCE.