DISPLAY MODE

Pressing the Display/Toggle pushbutton allows the

user to scroll through the Normal, Alternate and Menu
display Modes.

ALTERNATE DISPLAY MODE

Alternate Display Mode can be used to observe

generator performance  including oil pressure, coolant
temperature, battery voltage, kilowatt load, generator
voltage, kVA, hours to next service, amps, generator
frequency, total run hours, engine speed, and unit
identification number.

After pressing the Display/Toggle pushbutton to

enter the alternate display mode, pressing the
Raise/Scroll or Lower/Scroll pushbutton allows the user
to scroll through the alternate display mode screens.

MENU MODE

Menu Mode can be used to observe settings

programmed into the control panel. The menus include
information on alarms, system configuration, sensing
devices, and engine parameters.

To access the Menu Mode press the Display/Toggle

(if in Normal Mode) pushbutton twice to begin the Menu
display. Options can be selected by pressing the
Raise/Scroll or Lower/Scroll pushbuttons, and after
locating the desired option, pressing Select/Enter begins
the next level of menus.

RUN MODES

There are three run mode options: RunOff and

Auto. When the Run pushbutton is pressed the unit will
immediately start and the “not in auto” light will illuminate.
In Run mode, the generator will continue to run until the
Off pushbutton is pressed to stop the unit. At this point
the “not in auto” light will illuminate and the unit will not
operate.

When the Auto pushbutton is pressed the unit will

enter automatic run mode, where the generator controller
and the transfer switch will control the operation of the
unit. In automatic run mode, the unit will automatically
start up and shut off when power failure occurs and to
exercise the unit. 

When power failure occurs, a signal will be sent to

the generator to start a warm up cycle. After the warm up
cycle is completed, the transfer switch will allow the load
to be transferred to the generator until it senses that
regular utility power has been restored. When this
occurs, the transfer switch will remove the load from the
generator and a signal will be sent to the generator to
begin a cool down cycle. After the cool down cycle is
completed, the unit will stop running, but remain in the
automatic run mode.

The unit will also automatically start itself to ensure it

remains in good working order. Every 14 days the unit
will automatically start up without warning and run for 20
minutes before shutting down. The unit will remain in
automatic run mode after each exercise session.

G

G

E

E

N

N

E

E

R

R

A

A

T

T

O

O

R

R

 

 

C

C

O

O

N

N

T

T

R

R

O

O

L

L

P

P

A

A

N

N

E

E

L

L

O

O

P

P

E

E

R

R

A

A

T

T

I

I

O

O

N

N

W

WA

AR

RN

NIIN

NG

G

The unit will automatically start and stop 
without notice.

15

Summary of Contents for Powermate PM402511

Page 1: ...umbers of your generator below Model Number ____________________ Serial Number ____________________ Date Purchased ____________________ HELPLINE 1 800 445 1805 OWNERS MANUAL MODEL PM402511 Read and understand all safety precautions in this manual and other manuals included with this product before installing operating and maintaining this equipment Failure to comply with instructions in this manua...

Page 2: ...Control Panel Features 14 Generator Control Panel Operation 15 Generator Control Panel Alarms 16 Overcrank Alarm 16 Overspeed Alarm 16 High Coolant Temperature Alarm 16 Low Oil Pressure Alarm 16 Engine Sender Fault Alarm 16 Low Coolant Level Alarm 16 Generator Control Panel Pre Alarms 16 High Coolant Temperature Pre Alarm 16 Low Coolant Temperature Pre Alarm 16 Weak Battery Pre Alarm 16 Battery Ov...

Page 3: ... or death Install the generator set outdoors only Do not use exhaust air to heat a room Do not allow exhaust air to enter a building through windows doors air intakes or other means Avoid breathing exhaust air while installing operating or servicing generator set The engine exhaust from this product contains chemicals known to the State of California to cause cancer birth defects or other reproduc...

Page 4: ...empt to free the victim from the live conductor AVOID DIRECT CONTACT WITH THE VICTIM Use a nonconducting implement such as a rope or board to free the victim from the live conductor If the victim is unconscious apply first aid and get immediate medical help Units with broken or missing parts without protective housing or covers should never be operated Contact your service center for replacement p...

Page 5: ...ge is noted after delivery segregate the damaged material and contact the carrier for claim procedures Be sure to retain the packaging material for carrier inspection Concealed Damage is understood to mean damage to the contents of a package which is not evident at the time of delivery by the carrier but which is discovered later The carrier or carriers are responsible for merchandise lost or dama...

Page 6: ...0 qt 3 79L without filter 4 50 qt 4 26L with filter change Oil filter Motorcraft FL400 Radiator capacity 2 5 gallons 9 46L Shipped with 50 50 mix of water and propylene glycol antifreeze Spark plug Motorcraft AWSF 52C Battery BCI Group minimum 550 CCA Air filter Contact factory Minimum Content Requirements 1000 Btus per cubic foot for Natural Gas NG 2520 Btus per cubic foot for Liquid Propane vapo...

Page 7: ...I IN NS ST TA AL LL LA AT TI IO ON N D DR RA AW WI IN NG GS S 7 ...

Page 8: ... should be tightened in the identified terminal block to 120 lb in The wire size is to be selected according to allowable ampacities given in Table 310 16 of the National Electric Code Field wiring of this unit must be conducted by a licensed electrician C CA AU UT TI IO ON N Covering or restricting the air passages on the generator will cause the unit to overheat and may create a fire hazard Do n...

Page 9: ...in carbon monoxide which can be DEADLY This dangerous gas if breathed in sufficient concentrations can cause unconsciousness or even death The generator must be installed properly in strict compliance with applicable codes and standards Following installation you must do nothing that might render the generator unsafe or in noncompliance with such codes and standards Considerations for proper rooft...

Page 10: ... Gas NG and 2520 BTU s per Cubic foot for Liquid Propane vapor LPG Contact local fuel supplier for local BTU content Fuel supply pressures must be between 4oz 7 H20 per square inch and 6oz 11 H20 per square inch at the inlet to the unit FUEL CONSUMPTION The PowerStation 25Kw at full load consumes 306 000 BTU s per hour of natural gas NG and 354 000 BTU s per hour of liquid propane vapor LPG F FU U...

Page 11: ... switch A AU UT TO OM MA AT TI IC C T TR RA AN NS SF FE ER R S SW WI IT TC CH H W WA AR RN NI IN NG G Hazardous backfeed voltage can cause severe injury or death Install a transfer switch in standby power installations to prevent connection of standby and other sources of power Electrical backfeed into a utility electrical system can cause serious injury or death to utility personnel working on tr...

Page 12: ...use a solution of one pound 500 grams bicarbonate of soda to one gallon 4 liters of water The bicarbonate of soda solution is to be added until the evidence of reaction foaming has ceased The resulting liquid is to be flushed with water and the area dried A battery presents a risk of electrical shock and a high short circuit current The following precautions are to be observed when working on batt...

Page 13: ...cate any problems that the generator may have due to installation or shipping Before starting the generator read and understand the operation of the controller panel After becoming familiar with the controller operation start the generator set by pressing the RUN button L LU UB BR RI IC CA AT TI IO ON N A AN ND D C CO OO OL LI IN NG G W WA AR RN NI IN NG G Hot coolant under pressure in radiator ca...

Page 14: ...the unit in the OFF mode J Red LED turns ON when the device is in the OFF mode K Pushbutton used to place the device in the RUN mode L Green LED turns ON when the device is in the RUN mode M Pushbutton used to scroll through the displays available in the normal display mode N Pushbutton used to scroll through the display modes O Pushbutton used to scroll through previous menu levels P Pushbutton u...

Page 15: ...ill illuminate In Run mode the generator will continue to run until the Off pushbutton is pressed to stop the unit At this point the not in auto light will illuminate and the unit will not operate When the Auto pushbutton is pressed the unit will enter automatic run mode where the generator controller and the transfer switch will control the operation of the unit In automatic run mode the unit wil...

Page 16: ...ure and Battery Voltage pre alarms are shown on the main display with their current values alternately flashing All other pre alarms are individually displayed in sequence using the alternate main display mode whereby each pre alarm value is alternately flashed All pre alarmed parameters are displayed in this manner before non pre alarmed parameters All pre alarms are reset by correcting the cause...

Page 17: ... 5K KW W W WI IR RI IN NG G D DI IA AG GR RA AM M C CP P5 50 00 0 C CO ON NT TR RO OL LL LE ER R SCHÉMA DE CÂBLAGE 25KW CONTRÔLEUR CP 500 DIAGRAMA DE CIRCUITO ELÉCTRICO DE 25 KILOVATIOS CONTROLADOR CP500 17 ...

Page 18: ... KW W W WI IR RI IN NG G D DI IA AG GR RA AM M C CP P1 10 00 00 0 C CO ON NT TR RO OL LL LE ER R SCHÉMA DE CÂBLAGE 25KW CONTRÔLEUR CP 1000 DIAGRAMA DE CIRCUITO ELÉCTRICO DE 25 KILOVATIOS CONTROLADOR CP1000 18 ...

Page 19: ...ccordance with applicable codes Engine block heater can cause electrical shock Remove engine block heater plug from electrical outlet before working on block heater connections Improper service or replacement of parts can lead to severe personal injury or death and to damage to equipment and property Service personnel must be qualified to perform electrical and mechanical service Use caution when ...

Page 20: ...ective connections 3 Defective alternator 4 Defective battery charger 1 Insufficient fuel volume 2 Engine electrical problem 3 Engine configured for wrong fuel 4 Generator over loaded CORRECTIVE ACTION Recharge or replace battery Replace fuse Check and clean D C connections Call customer service Call customer service Call customer service Check fuel supply and manual operated fuel valves Call cust...

Page 21: ...used by operation with improper fuel or at speeds loads conditions modifications or installation contrary to published specifications or recommendations Damage caused by negligent maintenance such as Failing to provide the specified type and sufficient quantity of lubricating oil Failing to keep the air intake and cooling areas clean Failing to service the air cleaner Failing to provide sufficient...

Page 22: ...hich is performed Noting the time on the hour meter will help in keeping the maintenance schedule All safety rules must be followed when performing maintenance on the unit Be sure the engine is not running when performing maintenance Check oil level every 8 hours of operation Change oil and filter every 100 hours Change air filter every 400 hours Replace spark plugs every 500 hours Check radiator ...

Page 23: ...1 2 long Perno 13X1 1 2 LG 10 0058212 1 Exhaust gasket Joint d échappement Junta de escape 11 026 0357 1 Exhaust tube wrap Enveloppe de tuyau d échappement Cubierta del tubo de escape no Not shown in drawing non illustré aparece en el esquema 12 0056778 6 Clamp stainless steel for exhaust Bride acier inoxydable pour Abrazadera acero inoxidable wrap Not shown in drawing enveloppe de tuyau d échappe...

Page 24: ...al a prueba proofing material de ruido 6 115 0209 1 Exhaust cover panel Panneau couvre échappement Panel de cubierta del escape 7 115 0210 1 End panel Panneau d extrémité Panel terminal 8 1 Frame Châssis Estructura 9 115 0211 1 Radiator panel Panneau de radiateur Panel del radiador 10 115 0212 1 Door assembly inner inlet Ensemble de porte intérieure à Conjunto de puerta entrada includes hinges doo...

Page 25: ...or 6 0058017 1 Radiator Radiateur Radiador 7 077 0167 1 Radiator cap 14 psi Bouchon de radiateur 14 psi Tapa del radiador 14 psi 8 080 0066 2 Tube ID 3 16 X 1 16 wall Tuyau D I 3 16 X 1 16 d épaisseur Tubo pared DI 3 16 X 1 16 9 0058022 1 Radiator overflow bottle assy Bouteille de trop plein de radiateur Recipiente de rebase del radiador 10 115 0129 1 Radiator fan shield Écran de ventilateur de ra...

Page 26: ...0111 1 2 Point rod control includes Contrôle de tige 2 points Control de varilla de 2 puntas item 9 qty 2 incluant article n 9 qté 2 incluye el artículo N º 9 Cantidad 2 12 Order item 16 1 Nut Écrou commander article n 16 Tuerca Pida el artículo N 16 13 093 0049 4 Grommet Passe fil Ojal 14 0058035 2 Door hinge assembly LH surface Ensemble de charnières Main Conjunto de bisagra de puerta screw on n...

Page 27: ...a de manguera 1 ID 5 012 0091 2 Hose vapor 51 ID Tuyau vapeur D I 0 51 Manguera vapor 0 51 ID 6 0058274 4 Clamp P 938 Bride P 0 938 Abrazadera P 0 938 7 N A 2 Bolt HH 1 4 20 X 75 Boulon HH 1 4 20 X 0 75 Perno HH 20 X 0 75 8 068 0076 3 Fitting 3 4 NPT x 1 2 barb Raccord 3 4 NPT x 1 2 cannelé Acoples 3 4 NPT x 9 019 0203 1 Regulator LPG NG Régulateur GPL GN Regulador LPG NG 10 0057345 01 2 Solenoid ...

Page 28: ...citation Rotor excitador 3 0059182 1 Complete rotor Rotor complet Rotor completo 4 0059181 1 Complete main stator Stator principal complet Estator principal completo 5 0059190 1 AVR Régulateur de tension AVR AVR 6 0059186 1 Bearing N D E Roulement N D E Cojinete N D E 7 0059185 1 Bearing O ring N D E Joint torique de roulement N D E Junta tórica de cojinete N D E 8 0059184 1 Exciter stator Stator ...

Page 29: ... 10 14 X 63 12 S115 0140 1 Exhaust plenium cover Couvercle de gaine Cubierta del pleno del escape exhaust side d échappement côté échappement lado del escape 13 115 0125 1 Exhaust plenium exhaust side Gaine d échappement côté Pleno del escape lado del échappement escape 14 098 2633 2 Label warning Étiquette de mise en garde Etiqueta advertencia 15 0058012 1 Generator head Newage see Tête de généra...

Page 30: ... 1 4 turn pawl Verrou 1 4 de tour no 10 Cerradura retén de vuelta N 10 13 Order item 10 1 Control panel door Porte du tableau de commande no 10 Puerta del panel de control N 10 14 Order item 10 1 Control panel door hinge not shown Charnières de porte du tableau de Bisagra de la puerta del panel de commande non illustré no 10 control no se muestra N 10 15 N A 2 Bolt HH 1 4 20 x 75 Boulon HH 1 4 20 ...

Page 31: ...over Couvercle de boîte de jonction Cubierta de la caja de empalme 14 0058024 1 Terminal block 2 Row 175A 3 Pole Plaquette de connexion 2 rangées Bloque de terminales 2 hileras 175A 3 pôles 175 amperios 3 polos 15 0058025 1 Terminal block 2 Row 20A 3 Pole Plaquette de connexion 2 rangées Bloque de terminales 2 hileras 20A 3 pôles 20 amperios 3 polos 16 026 0411 1 Wire harness engine Harnais à fils...

Page 32: ...n de batería 3 026 0444 1 Battery cable positive Câble de batterie positif Cable de batería positivo 4 026 0445 1 Battery cable negative Câble de batterie négatif Cable de batería negativo 5 N A 1 Battery BCI Group 26 vented Batterie ventilée Groupe BCI 26 Batería Grupo BCI 26 ventilada 6 098 2701 1 Label warning Étiquette de mise en garde Etiqueta advertencia N A These are standard parts availabl...

Reviews: