246801-CTG-C-0407
4
Unitary Products Group
AIR FLOW DATA
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM
JUMPER SETTINGS
CFM
CFM
High
Low
High
Low
COOL
Tap
ADJ Tap*
1342
872
1650
1073
A
B
1155
751
1540
1001
B
B
1220
793
1500
975
A
A
1050
683
1400
910
B
A
1098
714
1350
878
A
C
913
593
1320
858
C
B
945
614
1260
819
B
C
726
472
1100
715
D
B
830
540
1200
780
C
A
660
429
1000
650
D
A
747
486
1080
702
C
C
594
386
900
585
D
C
JUMPER SETTINGS
CFM
CFM
High
Low
High
Low
COOL
Tap
ADJ Tap*
1650
1073
2052
1334
A
B
1540
1001
1760
1144
B
B
1500
975
1865
1212
A
A
1400
910
1600
1040
B
A
1350
878
1679
1091
A
C
1320
858
1540
1001
C
B
1260
819
1440
936
B
C
1100
715
1320
858
D
B
1200
780
1400
910
C
A
1000
650
1200
780
D
A
1080
702
1260
819
C
C
900
585
1080
702
D
C
JUMPER SETTINGS
CFM
High
Low
COOL
Tap
ADJ Tap*
2052
1333
A
B
1760
1144
B
B
1865
1212
A
A
1600
1040
B
A
1679
1091
A
C
1540
1001
C
B
1440
936
B
C
1320
858
D
B
1400
910
C
A
1200
780
D
A
1260
819
C
C
1080
702
D
C
HIGH / LOW HEAT CFM
(F,L)C8V060A12DH11
(F,L)C8V080B16DH11
JUMPER SETTINGS
CFM
CFM
High
Low
High
Low
HEAT Tap
ADJ Tap*
1350
1013
1900
1425
A
Any
1250
938
1750
1313
B
Any
1150
863
1650
1238
C
Any
1050
788
1400
1050
D
Any
(F,L)C8V100C16DH11
(F,L)C8V100C20DH11
JUMPER SETTINGS
CFM
CFM
High
Low
High
Low
HEAT Tap
ADJ Tap*
2100
1575
2100
1575
A
Any
2000
1500
2000
1500
B
Any
1800
1350
1800
1350
C
Any
1700
1275
1700
1275
D
Any
(F,L)C8V120C20DH11
JUMPER SETTINGS
CFM
High
Low
HEAT Tap
ADJ Tap*
2350
1998
A
Any
2250
1913
B
Any
2000
1700
C
Any
1800
1530
D
Any
All CFM’s are shown at 0.5” w.c. external static pressure. These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to 0.6” w.c. static pressure.
From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static.
Operation on duct systems with greater than 1.0” w.c. external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the
instructions for the electronic air cleaner for further details.
NOTE: The ADJ “D” tap should not be used.
1 CFM = 0.028316847 m3/min