266180-BIM-B-0209
Johnson Controls Unitary Products
7
Casing or cabinet must be permanently grounded in accordance with National Electrical Code or other applicable codes.
1. Approved for Single Branch Circuit Service Only.
TABLE 3:
EB Series Blower Performance
Static Pressure (inches of w.c.)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Low Speed - Heating Speed
Models EB10, 12, 15
CFM (STD. Air)
945
936
936
924
915
889
870
813
705
Medium Speed - Heating Speed
Models EB17, 20, 23
CFM (STD. Air)
1160
1145
1145
1140
1129
1109
1073
1027
935
Medium High - with A-Coil in place
CFM (STD. Air)
1340
1317
1290
1252
1208
1158
1095
1021
876
High - with A-Coil in place
CFM (STD. Air)
1573
1534
1490
1435
1369
1309
1237
1135
1019
TABLE 4:
Electrical Data
MODEL NUMBER
EB23C
EB20C
EB17C
EB15C
EB12C
EB10C
D.O.E.
Output
240 VAC
60 Hz.
1 Phase
BTU
77,000
67,000
56,000
51,000
39,000
34,000
kW
22.6
19.6
16.4
15.0
11.4
10.0
OUTPUT
CAPACITY
230 VAC
60 Hz.
1 Phase
BTU
71,000
61,000
52,000
47,000
36,000
31,000
kW
20.8
17.9
15.2
13.8
10.6
9.1
220 VAC
60 Hz.
1 Phase
BTU
65,000
57,000
48,000
43,000
33,000
29,000
kW
19.1
16.7
14.1
12.6
9.7
8.5
Element Capacity
@ 240 VAC
kW
21.6
19.2
16.0
14.4
11.2
9.6
Amps
90.0
80.0
66.7
60.0
46.7
40.0
Motor Amps @ 240 V.
4.0 Maximum
Circuit Load Amps
@ 240 V.
CKT 1
47.3
44.0
47.3
44.0
50.7
1
44.0
1
CKT 2
46.7
40.0
23.4
20.0
NA
NA
FIGURE 12:
Control Box
Sequencers
Circuit Breakers
Thermostat
Wires
Blower
Rela
y
Transformer
Limit
Switches
Ground
Lugs
3500-378P* Jumper
Bars (For Single
Branch Circuit Service)
NOTE:
As Shipped, the Jumper Bar Assembl
y
is Set-up for Bottom Entr
y
. For Side
Entr
y
, the Top Lug can be Removed and
Re-positioned, as Shown, to Provide
Proper Wire Bending Clearances.