Unitary Products Group
TABLE 19: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
USED FOR
A
7/8” KO
1
1.
Opening in the bottom to the unit can be located by the
side in the insulation.
Control Wiring
2
2.
Do not remove the 2” knockout ring.
Side
Bottom
B
2” KO
1
Power Wiring
Side
Bottom
C
1-5/8” KO
Gas Piping (Front)
D
1-1/2” KO
Gas Piping (Bottom)
TABLE 20: MINIMUM CLEARANCES
LOCATION
CLEARANCE
Front
24” (Cooling/Electric Heat)
32” (Gas Heat)
Rear
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
Left Side (Filter Access)
24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil)
24”
Below Unit
1
1.
Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
0”
Above Unit
2
2.
Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
72” (For
Condenser Air Discharge)
TABLE 21: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
843
860
880
925
919
1005
956
1065
993
1145
1030
1195
1067
1235
1900
817
775
854
850
893
920
930
995
970
1065
1008
1125
1046
1170
1800
790
700
828
760
867
840
906
905
944
980
985
1040
1025
1100
1700
-
-
802670
840
745
881
815
92
0
900
961
970
1001
1030
1600
-
-
-
-
818
665
858
740
898
82 0
940
890
980
950
1500
-
-
-
-
-
-
842
695
882
755
92 2
835
962
895
1400
-
-
-
-
-
-
833
650
867
705
904
765
942
82 0
1300
-
-
-
-
-
-
-
-
858
665
893
72 5
932
785
12 00
-
-
-
-
-
-
-
-
847
640
880
680
916
730
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
1103
1270
-
-
-
-
-
-
-
-
-
-
-
-
1900
1085
1210
-
-
-
-
-
-
-
-
-
-
-
-
1800
1064
1145
11021180
-
-
-
-
-
-
-
-
-
-
1700
1040
1075
1081
1115
1121
1140
-
-
-
-
-
-
-
-
1600
1020
1005
1060
1050
1100
1085
-
-
-
-
-
-
-
-
1500
1003
945
1044
995
1086
1035
-
-
-
-
-
-
-
-
1400
982
880
1024
920
1067
965
1107
1000
-
-
-
-
-
-
1300
970
835
1010
870
1053
920
1099
960
-
-
-
-
-
-
1200
953
780
992
815
1034
855
1080
905
-
-
-
-
-
-
3
1
,
2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.90
1.00
1.10
1.20
1.30
1.40
1.50
UNIT
TONNAGE
AIR
FLOW
CFM
3
1
,
2
UNIT
TONNAGE
AIR
FLOW
CFM
0.60
0.70
0.80
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
3
0.20
0.30
0.40
0.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.