PERFORMANCE DATA - 5 TON
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
CONDENSER-ONLY DATA (OUTDOOR UNIT)
MODEL
SATURATED SUCTION
@ COMPRESSOR
Outdoor Ambient Temperature
55 °F
65 °F
75 °F
85 °F
95 °F
105 °F
115 °F
125 °F
T (°F)
P (PSIG)
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
AC19B6021S
(Stage 2)
35
107
56.0
3.18
53.3
3.46
50.6
3.79
47.8
4.17
44.8
4.61
41.7
5.13
38.3
5.73
34.7
6.42
40
118
61.4
3.21
58.6
3.49
55.6
3.81
52.6
4.18
49.4
4.61
46.0
5.13
42.4
5.72
38.5
6.40
45
130
67.0
3.26
64.2
3.53
61.0
3.84
57.7
4.20
54.2
4.62
50.6
5.13
46.7
5.72
42.6
6.38
50
142
73.0
3.32
69.6
3.59
65.9
3.90
62.6
4.24
59.4
4.65
55.5
5.14
51.4
5.72
46.9
6.37
55
156
78.3
3.40
75.8
3.65
72.0
3.96
68.4
4.29
64.7
4.68
60.6
5.17
56.2
5.74
51.6
6.36
AC19B6021S
(Stage 1)
35
107
37.1
2.20
35.0
2.51
33.1
2.85
31.1
3.22
28.8
3.64
26.2
4.14
23.2
4.70
19.8
5.34
40
118
41.0
2.14
38.8
2.46
36.7
2.79
34.5
3.16
32.1
3.58
29.4
4.07
26.3
4.63
22.8
5.26
45
130
45.2
2.09
42.8
2.40
40.5
2.74
38.1
3.11
35.6
3.52
32.8
4.00
29.6
4.56
25.9
5.18
50
142
49.8
2.05
47.1
2.35
44.5
2.68
42.0
3.04
39.3
3.45
36.3
3.93
33.0
4.48
29.2
5.09
55
156
54.6
1.98
51.6
2.29
48.9
2.62
46.1
2.97
43.2
3.38
40.1
3.85
36.6
4.40
32.7
5.00
Notes:
1. For Outdoor Unit (Condenser) performance only. Data does not include the effects of air handler power or heat.
2. Performance based on 15°F subcooling and 15°F superheat at the Outdoor Unit base valves.
a. Increase capacity by 1% for each 2°F increase in subcooling.
b. Decrease capacity by 1% for each 2°F decrease in subcooling.
3. Maximum recommended condensing temperature is 140°F.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
AC19B6021S
INDOOR COIL MODEL NO.
CF64DXA1
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
ID CFM
1500
1750
2000
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
55
T.C.
55.6
59.6
59.4
61.6
62.0
57.6
60.4
60.2
61.9
62.2
59.6
61.2
61.1
62.1
62.3
S.C.
54.2
46.9
40.5
37.7
29.2
56.5
48.5
41.8
38.5
29.5
58.7
50.2
43.1
39.3
29.9
KW
3.04
3.07
3.07
3.07
3.07
3.15
3.16
3.16
3.16
3.16
3.25
3.25
3.26
3.26
3.25
65
T.C.
54.0
58.0
57.8
61.5
64.5
56.1
59.1
58.9
62.2
65.2
58.2
60.3
60.1
62.9
65.9
S.C.
52.9
46.6
39.8
38.3
30.1
55.1
49.1
41.8
39.9
30.9
57.3
51.6
43.8
41.5
31.7
KW
3.35
3.38
3.38
3.40
3.42
3.45
3.48
3.48
3.50
3.52
3.55
3.57
3.58
3.59
3.61
75
T.C.
52.5
56.4
56.2
61.4
66.9
54.6
57.8
57.6
62.6
68.2
56.8
59.3
59.0
63.8
69.4
S.C.
51.6
46.2
39.1
38.8
31.1
53.7
49.7
41.8
41.2
32.3
55.9
53.1
44.4
43.6
33.5
KW
3.65
3.69
3.69
3.73
3.77
3.75
3.79
3.79
3.83
3.87
3.86
3.90
3.90
3.93
3.97
85
T.C.
51.2
54.4
54.2
59.2
64.2
53.4
55.8
55.6
60.3
65.5
55.6
57.2
56.9
61.4
66.8
S.C.
50.4
45.7
38.6
38.1
30.2
52.6
49.2
41.3
40.6
31.6
54.7
52.8
44.0
43.1
33.0
KW
4.05
4.09
4.09
4.13
4.18
4.16
4.20
4.19
4.24
4.28
4.27
4.30
4.30
4.34
4.38
95
T.C.
50.0
52.4
52.2
57.0
61.5
52.2
53.8
53.5
58.0
62.9
54.4
55.2
54.8
59.0
64.3
S.C.
49.2
45.2
38.0
37.4
29.3
51.4
48.8
40.8
40.0
31.0
53.6
52.4
43.6
42.6
32.6
KW
4.46
4.50
4.49
4.53
4.59
4.57
4.60
4.60
4.64
4.69
4.68
4.70
4.70
4.75
4.80
105
T.C.
46.7
48.7
48.6
53.2
58.1
48.9
50.1
49.7
54.2
59.1
51.1
51.6
50.9
55.2
60.1
S.C.
46.0
43.3
36.2
35.9
28.1
48.1
46.4
39.0
38.5
29.7
50.3
49.5
41.7
41.1
31.3
KW
5.06
5.09
5.08
5.13
5.18
5.17
5.19
5.19
5.24
5.28
5.28
5.29
5.29
5.34
5.39
115
T.C.
43.5
45.1
45.1
49.6
54.8
45.7
46.6
46.1
50.5
55.4
47.8
48.1
47.1
51.5
56.0
S.C.
42.9
41.4
34.6
34.4
26.9
45.0
44.1
37.2
37.0
28.5
47.1
46.7
39.8
39.6
30.0
KW
5.64
5.66
5.65
5.71
5.75
5.75
5.76
5.76
5.81
5.85
5.86
5.87
5.87
5.92
5.96
125
T.C.
40.4
41.5
41.6
46.0
51.6
42.5
43.1
42.4
46.8
51.8
44.6
44.7
43.3
47.7
51.9
S.C.
39.7
39.5
32.9
32.9
25.8
41.8
41.7
35.4
35.5
27.2
43.9
44.0
37.9
38.2
28.7
KW
6.22
6.23
6.22
6.29
6.32
6.33
6.34
6.34
6.39
6.43
6.44
6.44
6.45
6.50
6.53
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.