A
For the reader cable connection to the CODE Controller, CAT 5 cable or 8 core
twisted pair cable can be used.
B
The reader is normally installed at the right side of the door (outside) at a height
of 1.4m from the floor and 3-5 cm from the door frame, with the exit button
(inside) also at a height of 1.4m off the floor.
C
The reader should not be installed against a metal surface. If this can not be
avoided, either the metal surface should be removed, with only the fixing area
remaining, or an isolation material thicker than 10cm should be placed
between the reader and the metal surface.
D
The Controller to reader length should not exceed 60 metres using CAT 5 cable
E
Please observe reader power polarity when connecting to the access controller
Notes For Installation
Product Specification
Reader Parameters
Reader Radio Frequency: 13-56 MHz
Card Identification Mode: MF card
Sensing Distance: MF Card 2-4cm
Reader Data Output: Wiegand 26 Bit
Reading Speed: < 0.1s
Name
Qty Note
CODE-2641
1
Vandal Reader
User manual
1
User Documentation
Screw driver
1
Φ
20mm×60mm,Special for RF006
Rubber plug
2
Φ
6mm×30 mm, used for fixing
Self tapping screws 2
Φ
4mm×28 mm, used for fixing
Material
Metal
Operating Voltage
9-16V DC
Output
WG 26
Card type
Mifare
Reading Distance
2-4 cm
Communication Distance
60M
Idle Current
<80mA
Operating Temperature
-45
ºC ~
60
ºC
Operating Humidity
10%- 90% RH
Waterproof
Conforms to IP68
Dimension
120X56X18 mm
Packing List
Specification