Coalbrookdale MUCH WENLOCK Installation Instructions Manual Download Page 2

The recommended heating surface area is based on an
average heat emission of 0.5 kW/m

2

(160 Btu/h/ft

2

).

These figures are maxima and must not be exceeded.
A margin (about 10% or 1.4m

2

- 15ft

2

) is recommended.

The Much Wenlock Stove with Boiler is intended to
provide space heating and the heating of domestic hot
water and radiators has been approved by the HETAS LTD
Appliance Approval Scheme. The appliance and burning
rate are controlled by the manual adjustment setting of
the ashpit door spinwheel only.

1. A 140 litre capacity indirect hot water storage cylinder

of the double feed type, complying with BS 1566 Part
1: DF TYPE 8 should be lagged and fixed vertically as
near as possible to the stove.
The 28mm minimum diameter primary flow and return
pipes must not exceed 10m in length and pipes longer
than 5m must be lagged. Ensure that the flow pipe 
rises continuously from the stove boiler to the cylinder
to ensure good gravity circulation. In combined 
systems, the water draw-off pipes to the taps must be
dead-leg connections from the vent/expansion pipe.

2. One boiler flow connection (preferably that to the 

cylinder), must have an open vent. The connection to
the boiler must be such that air cannot be trapped in 
the boiler. Any pipe size reduction must be made on 
the vertical pipe of the vented flow pipe.
The heating flow and return pipes may be 22mm and
should preferably be connected to opposite tappings 
to each other on each side of the boiler.

3. All installations must be fitted with a drain tap at the 

lowest point of the system.

4. It is recommended that a gravity heat leak radiator 0.9

- 1.4m

2

(10-15ft

2

) heating surface be included, or a 

reverse acting cylinder thermostat to activate the 
pump in the event of overheating.

5. Long reach male fittings will be required to make 

pipework connection into the boiler.

For correct operation of the appliance, the height of the
chimney from its base should not be less than 5.5m and
terminate above the roof in accordance with current
Building Regulations Section J/1/2/3 and requirements as
outlined in BS 6461 Part 1 and BS 7566 Parts 1 to 4
should be observed.
The structural flue through the chimney should not be
less than 175mm diameter. Pargeted lined flues, 230mm
x 230mm must be in sound condition, and any internal
offsets should not be less than 60

˚

  to the horizontal.

Check that the flue exit is not obstructed or reduced in
size.

IMPORTANT:

FAILURE TO OBSERVE THE

RECOMMENDED MINIMUM SIZE OR METHODS OF
FLUE CONNECTION MAY LEAD TO EMISSION INTO
THE ROOM AND REDUCED BURNING RATES.

Existing Chimney

The internal and external condition of the chimney should
be checked 

before

the appliance is installed and

rectification made where necessary to prevent air leakage
or porosity.
The flue through the chimney should be formed with
175mm diameter minimum moisture and acid resistant
liners to BS 1181 or precast linings as specified in the
current Building Regulations and requirement in BS 6461
Part 1 and BS 7566 Parts 1 to 4 should be observed.
When repairing existing chimneys, it is recommended
that the Building Inspector be consulted before
commencement of work with particular attention to the
chimney height and its termination.

NOTE: THE CHIMNEY MUST BE SWEPT BEFORE
INSTALLATION.

Where the chimney is believed to have served an open
fire installation it is possible that the higher flue gas
temperature from a closed appliance may loosen
deposits that were previously firmly adhered, with the
consequent risk of flue blockage. It is therefore
recommended that the chimney be swept a second time
after one month of regular use.

New Chimney

The flue should not be less than 175mm diameter and its
soundness confirmed by smoke testing or consulting
HETAS LTD who will give advice on the test method.
Ensure the chimney liners are free of any internal
projections such as building jointing composition before
the appliance is installed.

Factory-made Insulated Chimneys

It is recommended that the internal face of the chimney,
be refractory lined and otherwise comply with BS 4543.
The recommended minimum diameter is 150mm and
chimney manufacturers should be consulted for further
advice.

HOT WATER SYSTEM

THE CHIMNEY

PERFORMANCE

2

Summary of Contents for MUCH WENLOCK

Page 1: ...e that the necessary personal protective clothing is worn when handling where applicable the pertinent parts that contain any of the listed materials that could be interpreted as being injurious to health and safety see below for information Firebricks Fuel beds Artificial Fuels when handling use disposable gloves Fire Cement when handling use disposable gloves Glues and Sealants exercise caution ...

Page 2: ... Regulations Section J 1 2 3 and requirements as outlined in BS 6461 Part 1 and BS 7566 Parts 1 to 4 should be observed The structural flue through the chimney should not be less than 175mm diameter Pargeted lined flues 230mm x 230mm must be in sound condition and any internal offsets should not be less than 60 to the horizontal Check that the flue exit is not obstructed or reduced in size IMPORTA...

Page 3: ...Water Undertaking Regulations for the Electrical Equipment of Buildings published by the Institute of Electrical Engineers and any relevant requirement of the Local Authority The appliance can be installed in a non combustible recess in which the hearth must be level and together with the adjacent walls conform to the current Building Regulations See Figs 1b and 2a A rectangular recess is required...

Page 4: ...amined for soundness and if necessary re sealed before installation After unpacking the stove remove all packaged parts from inside the stove and inspect the stove to ensure no damage gas occurred during delivery If there is a problem contact your local stockist Packaged parts contain a Flue Outlet Blanking Plate Flue Collar for top or back outlet and Operating Tool Support Collar Cradle complete ...

Page 5: ... complete stove 184Kg Bottomgrate bars there are six grate bars of one type and seven of another The seven bar occupy the ends and intermediate positions The six bars fit between these See that they are properly placed on the cross front firebar and move freely when riddled Flue Pipes C I Pipes and bends of 150mm diameter painted black are available through your local stockist Replacement parts if...

Page 6: ...6 ...

Page 7: ...7 ...

Page 8: ... product improvement the Company reserves the right to change specifications and make modifications to the appliance described and illustrated at any time Manufactured By Aga Rayburn Station Road Ketley Telford Shropshire TF1 5AQ England www aga rayburn co uk www agacookshop co uk www agalinks com www cookcraft com ...

Reviews: