CO2 Meter RAD-0002 Operating Manual Download Page 4

The large LCD displays the ambient O2 concentration. 

The SEU has the “DIAG”, “O2 AL1(Depletion)”, “O2 AL2(Depletion)”,”O2 AL3(Depletion)”, “O2 

AL1(Enrichment)”, “O2 AL2(Enrichment)”,”O2 AL3(Enrichment)”, “O2 CALI”, “RCFS” function. The 

“DIAG” function executes communication tests between the SEU and RDU. The user can do the 

calibration under the “CALI” mode when necessary. If data setting is done incorrectly, the user can use 

the “ReFactSet” mode back to the original factory setting.

There are “O2 AL1(Depletion)”, “O2 AL2(Depletion)” “ O2 AL3(Depletion)”  three alarm levels for 

O2 Depletion, these alarm levels are adjustable.

The AL1

 

(Depletion) of O2 is with parameter 18.0%

18.5%

19.0%

19.5%

20%,

 

the default 

AL1 is

 

19.0%.

The AL2

 

(Depletion) of O2 is with parameter 16.0

16.5%

17.0%

17.5%; the default AL2 is

 

17.0%.
The AL3

 

(Depletion) of O2 is 

12%.

When the RAD-0002 Monitor detects O2 value lowers than the O2 AL1(Depletion) , operate Alarm 1 

LED, Fault LED ,Relay 1, Audible, Strobe(if exist), till RESET on SEU regardless the rise of O2 level.

When O2 levels continue decaying, and below O2 AL2(Depletion): operate Alarm 1 LED, Alarm2 LED, 

Relay 1, Relay2, Audible, Strobe, Fault LED, till RESET on SEU regardless the rise of O2 level.

When O2 levels continue to decay, and below O2 AL3(Depletion): operate Alarm 1 LED, Alarm2 LED, 

Alarm3 LED, Fault indicator LED, Relay 1, Relay2, Relay3 Audible, Strobe, till RESET on SEU 

regardless the rise of O2 level.

There are “O2 AL1(Enrichment)”, “O2 AL2(Enrichment)” “ O2 AL3(Enrichment)”  three alarm 

levels for O2 Enrichment, these alarm levels are adjustable.

The AL1

 

(Enrichment) of O2 is with parameter 22.0, 22.5, 23.0, 23.5. (Default setting 

22.0%.)

The AL2

 

(Enrichment) of O2 is with parameter 24.0, 24.5, 25.0. (Default setting 24.0%.)

The AL3

 

(Enrichment) of O2 is with parameter 25%.

When the RAD-0002 Monitor detects O2 value higher than the O2 AL1 (Enrichment), operate Alarm 1 

LED, Fault LED, Relay 1, Audible, Strobe(if exist), till RESET on SEU regardless the decay of O2 level.

When O2 levels continue rising, and upon O2 AL2(Enrichment): operate Alarm 1 LED, Alarm2 LED, 

Relay 1, Relay2, Audible, Strobe, Fault LED, till RESET on SEU regardless the decay of O2 level.

When O2 levels continue rising, and upon O2 AL3(Enrichment): operate Alarm 1 LED, Alarm2 LED, 

Alarm3 LED, Fault indicator LED, Relay 1, Relay2, Relay3 Audible, Strobe, till RESET on SEU 

regardless the decay of O2 level.

If the communication cable between the SEU & RDU doesn’t connect well, like the communication cable 

looses in the Input port, the fault LED of SEU will blink, remind user reconnect the cable. If the 

communication cable is inserted into the wrong port on RDU, after about one minute, the “Er7” will flash 

on RDU LCD. 

Please plug it into the right port on RDU, the unit will work normally after corrective action.

4

.

SEU (Sensor Unit) Function Instructions

Summary of Contents for RAD-0002

Page 1: ...he oxygen concentration falls below 19 5 per OSHA requirements The RAD 0002 O2 Monitor is cost effective and has many features including Separate SEU Main Sensor Unit and RDU Remote Display Unit allow...

Page 2: ...O Battery Backup Input P DC Power Supply Q RDU Cable RJ45 R Relay 3 for AL3 S Relay 2 for AL2 T Relay 1 for AL1 U Strobe Cable RJ45 V Mount Panel Holder RDU Remote Display Unit A Power Green LED B Al...

Page 3: ...and this status will be latched AL1 Enrichment O2 The relay 1 will be triggered when O2 concentration higher than AL1 The Red 1 LED and Fault LEDs will flash buzzer will sound and relay1 will be acti...

Page 4: ...indicator LED Relay 1 Relay2 Relay3 Audible Strobe till RESET on SEU regardless the rise of O2 level There are O2 AL1 Enrichment O2 AL2 Enrichment O2 AL3 Enrichment three alarm levels for O2 Enrichmen...

Page 5: ...the terminal block 24VAC must be converted to 24VDC for the monitor to operate 8 Installation 1 First choose a suitable location near a wall outlet to install the main sensor unit or SEU You should u...

Page 6: ...y connected the yellow fault LED on the SEU will blink after startup If the cable is inserted into the wrong port on the back of the RDU after about one minute Er7 will flash on the RDU display Secure...

Page 7: ...unction On Off The alarm ships with the LATCH function off this allows the device to work its way out of alarm status on its own The function can be switched to on meaning alarms will continue until t...

Page 8: ...und on the SEU and RDU simultaneously 1 4 Using the DIAG function 1 Press Mode until the DIAG icon flashes 2 Press Enter this five LED s will blink on the SEU and the buzzer will sound 3 This five LED...

Page 9: ...gh 16 0 16 5 17 0 17 5 4 Press Enter again save or press Mode not save quit the setting Setting the O2 Third Alarm parameter of depletion 1 Press Mode until the AL3 O2 icon flashes and depl displays 2...

Page 10: ...l begin flashing 8 After approximately 3 minutes the LCD will display either PASS or FAIL 9 If the LCD reads FAIL repeat the steps again If it displays PASS press Enter The display should now show 21...

Page 11: ...the buzzer of SEU and RDU sound simultaneously it indicates that SEU and RDU work normally 12 Safety Notes Warning Your safety is very important to us To ensure to use the product correctly and safet...

Page 12: ...ion is below first alarm level Response Time 20 30 minutes Operating Conditions Operating Temperature 32 F to 122 F 0 C to 50 C Humidity Range 0 95 RH non condensing Storage Conditions Storage Tempera...

Page 13: ...r5 flash Fault LED blink Power on again or press reset button if the Er5 always appear please contact with the local dealer 3 Er7 Internal Data Transmission Error Er7 flash Fault LED blink Er7 flash F...

Reviews: