Chapter 5 - MODBUS-RTU Communication
81
5.7 Parameter Code List
< Common >
Parameter
address
Description
Unit
Read/Write
Data value (HEX)
Note
0000
Inverter model
-
R
7: SV-ACtionMaster
0001 Inverter
capacity
-
R
0: 0.5Hp, 1: 1Hp, 2: 2Hp
3: 3Hp, 4:5Hp, 5: 5.4Hp
0002
Inverter input voltage
-
R
0: 220V class, 1:440V class
0003 Version
-
R
313043: Version 1.0C
353043: Version 5.0C
0004
Parameter write enable
-
R/W
0: Write disable (default)
1: Write enable
0005
Reference frequency
0.01 Hz
R/W
0006 Operation
reference
-
R/W
Bit 0: Stop (R/W)
Bit 1: Forward (R/W)
Bit 2: Reverse (R/W)
Bit 3: Fault reset (W)
Bit 4: Emergency stop (W)
0007
Accel time
0.1 sec
R/W
0008
Decel time
0.1 sec
R/W
0009 Output
current
0.1
A
R
000A Output
frequency
0.01
Hz
R
000B Output
voltage
1
V
R
000C
DC Link voltage
000D Output
power
Not
used
000E Operating
status
-
R
Bit 0: Stop
Bit 1: Forward
Bit 2: Reverse
Bit 3: Fault (Trip)
Bit 4: Accelerating
Bit 5: Decelerating
Bit 6: Speed reached
Bit 7: DC Braking
000F Trip
info
-
R
Bit 0: OC
Bit 1: OV
Bit 2: EXT
Bit 3: BX
Bit 4: LV
Bit 5: Fuse Open
Bit 6: GF
Bit 7: OH
0010
Input terminal info
-
R
Bit 0: FX
Bit 1: RX
Summary of Contents for SV008ACtionMaster-2
Page 67: ...Chapter 4 Parameter Description FU2 61 Notes...
Page 105: ...Chapter 6 Troubleshooting Maintenance 99 Notes...
Page 109: ...Chapter 7 Options 103 Notes...
Page 118: ...112...