Instrument

Mid-West

®

 
 

 
 
 

ELECTRICAL

 

 

Gauges with switches have one or two SPST or SPDT 
hermetically sealed adjustable set point reed switch 
assemblies.  Resistive load ratings and capabilities for each 
reed switch type are defined as follows:   
 

Type SPST(Norm 

Open) 

SPDT 

*Power 25 

3W 

Max. Current 

0.5 Amps 

0.25 Amps 

Max. Voltage 

240 VAC/VDC 

125 VAC/VDC 

Setting (F.S.) 

15% to 90% 

15% to 90% 

Hysterisis 
(Max/Nom) 

15% / 8% 
Full Scale(F.S.) 

10% / 5% 
Full 
Scale(F.S.) 

Repeatability 

1% F.S. 

1% F.S. 

 

*   

Product of the switching voltage and current shall  
not exceed the power rating of the device.

   

 
Provide standard protection techniques for the switch 
contacts for capacitive and inductive loads.   Use current 
limiting techniques  near the switch to protect the contacts 
due to high inrush (i.e.; in line resistor or inductor) for long 
cable interfaces.  Provide clamping devices at or near 
inductive loads (i.e.; relay).  Long cable runs can be 
considered  both  inductive and capacitive, therefore also 
clamp across the switch.  We recommend for 

long cable

 

runs of 70 feet or greater that you use the SPST switch or 
use a current limiting resistor wired in series and located near 
the switch.  Contact the factory if you need assistance.  
Please note that the SPST switch is available in only the 

Normally Open

 configuration 

 

Both switch types are field adjustable from 15% to 90% of full 
scale reading of the gauge..  All switches come with a decal 
to identify adjustment direction to increase the set point.   To 
set the switch at a desired set point on increasing pressure 
apply pressure to the gauge for the desired set point.  Adjust 
the switch so that it is adjusted above the set point (normally 
open contacts are open) and slowly decrease the set point 
until the switch activates (normally open contact closes).  
Remove pressure and slowly reapply to determine the actual 
setting.  This process can be repeated to achieve a more 
accurate setting.  
 
All switch functionalities shown are with the gauge at 0 PSID.  
The SPST switches are available in the Normally Open 
configuration only. 

 

Use the Mid-West Power Relay 1000TR or equivalent relay  
for loads above the switch rating.  
 
 
 

 

 

 

 

 

 

 
 
 
 
 
 
The following warnings apply to all gauge options with 
electrical interface

 

 
WARNING:

 

ELECTRICAL CONNECTIONS SHOULD  

    

 

BE PERFORMED BY QUALIFIED 

    

 

PERSONNEL AND MEET THE   

    

 

REPRESENTATIVE COUNTRY'S  

    

 

NATIONAL ELECTRICAL CODE. 

 
WARNING:  FAILURE TO CONNECT TO THE  
  

PROTECTIVE 

CONDUCTOR 

TERMINAL 

    

 

MAY RESULT IN A SHOCK HAZARD. 

 

WARNING:  REMOVAL OR REPLACEMENT OF  
    

 

INSTRUMENT HARDWARE VOIDS ALL  

    

 

WARRANTIES AND CONFORMANCES TO  

    

 

ANY STANDARDS (EXCEPT COVERS 

   

 

AND OR SWITCH ADJUST PLUGS). 

 
NEMA 4X (Plastic Weatherproof Enclosure) 
(A & B options)

 

 

The reed switch(es) are located inside the  enclosure, on the 
top of the pressure housing, and are connected to a 7 
position terminal strip.  An opening is provided at the rear 
of the enclosure for a 1/2" flexible weather-proof cable or 
conduit connector (supplied by customer).  Upon request the 
hole may be sized to accommodate a PG-11 cable gland 
connector.   
 
Remove the switch enclosure cover by removing the (4) 
screws.  Insert wires through an appropriate (not supplied) 
weatherproof connector into the enclosure and connect  to 
the terminal strip per the terminal strip diagram shown below 
or  on the underside of the switch enclosure cover. The 
center connection is for connection of a protective conductor 
and is connected to the body of the pressure gauge.  

 
 
 

 
 
 
 
 
The terminal strip will accept wires in the range of 22 Awg - 
16 Awg..  Reinstall  the cover, gasket, and (4) screws. (Fig. 
3) after connection of field wiring. 
 
Wiring for the SPST switches is connected between NO and 
CM connections on the terminal strip.  

Normally closed 

switches are not available

 
Access holes and plugs are provided for external adjustment 
of  the  switches if required.  

Gauge 
Front

NO  NC CM         CM  NC  NO
    SINGLE              DOUBLE

 

     

Model 140 Electrical 

Installation and Operating Instructions

 

CMC TECHNOLOGIES 

P

TY

 L

IMITED

 ACN: 47 085 991 224    ABN: 47 085 991 224 

 

Phone: 

 

+61 2 9669 4000   

 

 

 

Unit 19, 77 Bourke Rd 

Engineering &

 Fax: 

 

 +61 

9669 

4111 

    Alexandria 

Industrial

  

Email: 

 

[email protected]

  

 

NSW  2015 

Instrumentation

 Website:

 

www.cmctechnologies.com.au

  

 

AUSTRALIA 

 

Reviews: