background image

The chimney must extend at least 3 
feet above the highest point where it 
passes through the roof. In addition, 
the top of the chimney should be at 
least 2 feet above any portion of the 
building that is within 10 feet of the 
chimney. The best draft is achieved if 
the top of the fireplace opening to the 
top of the chimney is at least 15 feet. 
If this distance is less than 15 feet, a 
larger flue size may be necessary. 

CHIMNEY CAP

Every masonry chimney should have  
a chimney cap to terminate the  
masonry and protect the chimney. 
This cap can be precast concrete or 
cast in place concrete. The chimney 
cap should extend beyond the exterior 
face of the masonry and incorporate 
a drip slot or other characteristic to 

CLEARANCE TO  

COMBUSTIBLES

One of the most important fire safety 
requirements is the air space that  
separates the chimney from the  
combustible materials such as the 
framing. For interior chimneys this 
space must be a minimum of 2 inches. 
For an exterior chimney this space 
must be a minimum of 1 inch. This 
space insulates the chimney and 
minimizes the transfer of heat to  
combustible materials. It must not  
be filled except for required fire stop-
ping. When masonry fireplaces and 
chimneys are part of a masonry wall, 
combustible materials should reside not 
less than 12 inches from the outside 
surface of the flue lining or firebox. 

Exposed combustible trim and the 
edges of sheathing materials such as 
wood siding, flooring and drywall 
should be at least 8 inches from the 
inside surface of the fireplace or  
flue lining. 

Woodwork or other combustible 
materials should not be placed within 

FLASHING

Base and counter flashing should be 
installed at the chimney / roof surface. 
The base flashing should be installed 
first, on the faces of the chimney  
perpendicular to the ridge line with 
tabs at each corner. The flashing 
should extend a minimum of 4 inches 
along the roof surface. Counter flash-
ing should then be installed over the 
base flashing, inserted into the mortar 
joint 3/4 to 1 inch wide, and mortared 
solidly into place. The counter flashing 
should lap the base flashing by at least 
3 inches. If the flashing is installed in 
sections, the flashing higher up the roof 
line should lap over the lower flashing  
a minimum of 2 inches. All joints in  
the same base and counter flashing 
should be sealed thoroughly, with  
any exposed side of the bends in the 
flashing also sealed. 

the building. Warm air tends to flow 
out from upper rooms, while cold air 
flows down to the lower rooms in the 
house. If you determine that you need 
a permanent source of makeup air, 
contact a heating and ventilation  
specialist and discuss the various  
options. Fireplaces will exhaust  
100-cfm to 1,000-cfm depending on 
the size and intensity of the fire. 

REDUCING CREOSOTE 

BUILDUP

Burning wood and fossil fuels in the 
absence of adequate airflow causes 
incomplete combustion of the oils in 
the wood, which are off-gassed as 
volatiles in the smoke. As the smoke 
rises through the chimney it cools, 
causing water, carbon and volatiles 
to condense on the interior surfaces 
of the chimney flue. The black oily 
residue that builds up is referred to as 
creosote. Creosote deposits reduce the 
draft (airflow through the chimney) 
which increases the probability that 
the wood fire is not getting enough 
air for complete combustion. Since 
creosote is highly combustible, a thick 

prevent moisture penetration from the 
top of the masonry wall to interior of 
the chimney. The cap should never  
be cast tightly against the flue liner.  
A gap should be left to accommodate 
expansion and contraction of the flue 
lining. The gap at the top between  
the cap and the flue liner should be 
sealed with caulk to prevent water  
or moisture from entering the  
chimney. This is a maintenance joint 
that should be inspected on a regular 
basis to ensure water tightness. It 
should be replaced when necessary.   

The use of quality polysulfide, butyl 
or silicone rubber caulking compound 
is recommended. Oil based sealants 
do not perform well in this applica-
tion. Backer rod also is suggested to 
support the caulk around the flue. 

6 inches of the fireplace opening. 
Combustible materials that are within 
12 inches of the fireplace opening 
should not project more than 1/8 inch 
for each 1 inch distance from such  
an opening. 

BALANCING THE  

VENTILATION

In order for a fireplace to function 
properly, a natural supply of makeup 
air must be available to replace the 
exhausted air from the chimney. In 
older homes there is often enough 
leakage around doors and windows to 
provide this air. In newer, tightly built 
homes another source of air must be 
provided. Before lighting the fire, use 
a match stick or candle to determine 
if there is an updraft or a down draft 
in the chimney. If there is no updraft 
try cracking open a window or door 
to provide a source of air to the room. 
If insufficient air is present, you may 
need to locate other sources of air 
entering or being exhausted from the 
room. The use of exhaust fans and 
opening an attic or upstairs rooms 
may be a source of air flowing out of 

MATERIAL SPECIFICATIONS

Use only those materials conforming to the following specifications:
  A.  Concrete Block – conforming to ASTM C-90 Grade N, ASTM C-129.
  B.  Mortar Mix – ASTM C-270 Type N.
  C.  Concrete Mix – ASTM C-39 (for the hearth slab and chimney cap).
  D. Brick – ASTM C-55 (or 216 Grade-SW).
  E. Caulking – Polysulfide, Butyl, or silicone rubber.
  F. Flashing – Corrosion resistant metal. No aluminum.
  G. Clay Flue Liners – Clay Flue Lining Institute and ASTM C-315, C-1283.
  H. Firebrick – ASTM C-27 or C-1261 low duty 2 inches thick minimum.
  I.    Refractory Mortar – Non-water soluble refractory mortar is best for installing both firebrick  

and clay flues. Homemade mixes combining fireclay and mortar simply do not meet the code.  

Refractory parge for the smoke chamber must also be non-water soluble. All of the above must 

meet the high temperature requirements of the ASTM C-199 medium duty code.

 

J.      Dampers – Should be certified to have air filtration losses not to exceed 20 cubic feet per minute 

when in the closed position.  

 

K.     Steel  Angle – Must meet ASTM A-36 with minimum dimensions as specified in Chart II in each 

fireplace drawing.

Chimneys, con’t.

8

9

Reviews: