57
Precautions on wiring of power supply
•
Use a round crimp-style terminal for connection to the power supply terminal board. In case it cannot be used due to unavoidable
reasons, be sure to observe the following instructions.
•
Do not connect different gauge wires to the same power supply terminal. (Loose connections may cause overheating.)
•
When connecting wires of the same gauge, connect them according to the figure below.
•
Use the correct screwdriver to tighten the terminal screws. Small screwdrivers can damage the screw head and prevent
appropriate tightening.
•
Over-tightening the terminal screws can damage the screws.
•
Attach a ground fault circuit interrupter and fuse to the power supply line.
•
In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires so that outside force
cannot affect the terminals.
Specifications of standard wiring components
Door 1: compressor compartment and electrical parts: XT1
Unit (kW)
1-phase 3-phase
5/7/9 12~16 12~16
Maximum
overcurrent protector
(MOP)
20 30
Wiring size (mm
2
) 4 6 4
15
Unit power supply
1-phase
Unit power supply
3-phase
Stated values are maximum values (see electrical data for exact values).
NOTE
The ground fault circuit interrupter must be a high-speed type breaker of 30 mA (<0.1 s).
Summary of Contents for WSAN-YMi 21
Page 1: ...WSAN YMi 21 81 MANUAL...
Page 43: ...43 Hydraulic module 5 7 9 kW 12 14 16 kW...
Page 53: ...53 P 5 7 9 kW 12 14 16 kW...
Page 112: ...112 1 phase 5 7 9KW 15 ELECTRICAL SCHEMA...
Page 113: ...113 1 phase 12 14 16kW...
Page 114: ...114 3 phase 12 14 16kW 15 ELECTRICAL SCHEMA...
Page 153: ...153 20 CONTROLLER NAVIGATION MENU...
Page 154: ...154...