t
Max 7 units
t
Maximum length of the bus line: 700 m.
t
Maximum distance between 2 units: 300 m
t
Type of cable: shielded twisted pair cable Ø 0,8 mm. use an EIB/KNX cable
t
Possible connections: Tree, star, in/out bus, mixed
t
It is not possible to use a ring connection
t
No end-of-line resistor or terminator required
t
There must be suitable arresters to protect the serial lines from the effects of atmospheric discharges
t
The data line must be kept separate from the power conductors or powered at different voltage values and away from possible sources
of electrical interference