Admissible water flow-rates
Minimum (Qmin) and maximum (Qmax) admissible water flow for the unit to operate correctly.
PREMIUM SC
250.2
280.2
320.2
360.2
400.2
420.2
440.2
480.2
540.2
580.2
Qmin
[l/s]
15,3
20,1
20,1
21,6
39,4
39,4
39,4
32,3
32,3
32,3
Qmax
[l/s]
37,3
45,2
45,2
53,4
86,6
86,6
86,6
72,5
72,5
72,5
Exchanger operating range
Internal exchanger
DPr
DPw
PED (CE)
2450
1050
DPr = Maximum operating pressure on refrigerant side in kPa DPw = Maximum operating pressure on water side in kPa
Overload and control device calibrations
open
closed
value
High pressure switch
[kPa]
2000
1450
–
Antifreeze protection
[°C]
3
5.5
–
High pressure safety valve
[kPa]
–
–
2400
Low pressure safety valve
[kPa]
–
–
1650
Max no. of compressor starts per hour
[n°]
–
–
6
Discharge safety thermostat
[°C]
–
–
120