Page
10
4- COMMISSIONING
4.1- Fresh water circuit
Important notice: The fresh water circulation must be adequate to the fan coil capacity.
Check that this capacity is > or = as to the value specified on the central unit.
The compressor cannot run without fresh water circulation. Reduced or no water circu-
lation will cause freezing situation and might damage the evaporator coil because of ice.
The following safeties prevent the unit to be damaged by the lack of fresh water circula-
tion.
The fresh water circuit must be filled with water and antifreeze solution
(20%). The addition of antifreeze lowers the freezing point of the water and
adds an additional safety to the circuit. Check that the fresh water circuit
pressure gauge shows 1,5 bars.
This device stops the unit if the water flow stops below the preset minimum.
As explained at chapter 3.2, a safety flow switch is installed in the fresh
water circuit outlet manifold. It is very important to make sure that this
safety device is properly wired to the control box: To do this, it is possible
to simulate a lack of fresh water flow just pushing the lever inside the switch
protecting cup. Warning: The flow switch is connected to the main electri-
cal box and this check must be done by expert engineers only, keeping in
mind all the safety precautions.
a) Antifreeze solution:
b) Safety flow switch (option):
Summary of Contents for CWS 121RC
Page 3: ...Page 2 1 ELECTRICAL CONNECTIONS CWS Basic 121 161 201 251 ...
Page 9: ...Page 8 3 FRESH WATER CIRCUIT CWS Basic 121 161 201 251 ...
Page 10: ...Page 9 3 FRESH WATER CIRCUIT CWS Basic 121 161 201 251 ...
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ...Page 24 9 ELECTRICAL SCHEMATICS CWS Basic 121 161 201 251 ...
Page 25: ...Page 25 9 ELECTRICAL SCHEMATICS CWS Basic 121 161 201 251 ...
Page 26: ...Page 26 9 1 Codes of spare parts CWS Basic 121 161 201 251 16 CWS 121 161 201 251 ...