Installation guide ECOT, regulator

Taking into use

1.

  Make sure that the connections are made correctly. Turn 

on the 230V supply voltage coming to the supply air 
unit. The display (7) will show the room temperature and 
the LED (6) will light up. The factory setting of the regu-
lator is 21ºC (central point of the setting area) and if the 
room temperature is lower, the led will turn red and the 
heating will be switched on, otherwise a green led will 
be illuminated.

2.

 When the value of the regulator is changed (± 3ºC from 

the value of the central point) with the control knob (4), 
you can see the new setting value on the display (7).

3.

 Changing the central point of the setting area to e.g. 

24ºC. Open the cover (2) of the regulator and turn the 
temperature control knob (4) up (extreme position). Re-
move jumper S3 and install it back to its position. The 
new central point of the setting area will now be 24ºC.

4.

 The factory set accuracy of temperature adjustment is ± 

0.5ºC. If you need to change the accuracy to ± 1ºC, remo-
ve jumper S2. Temperature drop from the setting value 
of 3ºC...10ºC is adjusted from the knob (8).

5. 

The value of temperature drop is visible on the display 
(7).

6. 

After you have made all the necessary changes, reinstall 
the cover (2) and the system is ready for use.

Installation of the regulator:

1. 

Bring the cable intended for the regulator unit (KLMA) from the 
supply air unit either to the instrument box (60 mm spacing bet-
ween holes) or directly to a surface-mounted ECO regulator.

2. 

Remove the cover (2) of the regulator from the rear part (1), using 
e.g. a small screwdriver (clips at the upper and lower edge of the 
thermostat).

3. 

Fix the rear part of the regulator either to the instrument box or 
directly on the wall, using screws (3).

4. 

Connect the cables to the terminal block (5) as shown on Figure 2.

5.

 If the temperature drop function is taken into use, connect it as 

shown on Figure 5.

6.

 After all the connection work, check the connections and reinstall 

the cover of the regulator.

Parts of ECO regulator

1. 

Rear part

2.

 Cover

3.

 Fixing screw (to a wall, 2 pcs)

4. 

Temperature control knob

5.

 Terminal block

6. 

Signal LED

7. 

Temperature display

8. 

Control knob for changing the setting   
value of temperature drop

9.

 Jumpers S2 and S3

2

1

4

3

5

6

7

8

9

Z1

GO (0V)

CLOSED = DROP

OPEN= NO DROP

NPN CONDUCTS= DROP

NPN DOES NOT

CONDUCT= NO DROP

0V = DROP

10V = NO DROP

ECO-regulator

ECO-regulator

ECO-regulator

Z1

GO (0V)

Z1

GO (0V)

+

0/10V

-

Figure 4

Figure 5

Figure 6

1.

2.

Temperature drop alternatives of ECO regulator