Power In: 18-24V DC

100mA max

CL-AB-RF-W

Wiegand Converter

-

+

D0

D1

MODE

Circut

Breaker

MODE

Circut

Breaker

MODE

Circut

Breaker

MODE

Circut

Breaker

MODE

Circut

Breaker

MODE

Circut

Breaker

MODE

Circut

Breaker

MODE

Circut

Breaker

N

L

Magnec

 Door Lock

External

Power Supply

-

+

GND

In

5

7

6

8

Change Module Address

The module address can be set from 0 to 31 by means of a dip switch called “address selector switch”. 

Before changing module address the main power must be disconnected. The address must be defined 

in binary. For instance to set address “19”, the dip switch must be as below: 

Module’s LEDs

Power: 

When the module is connected to main power, “Power LED” will flash smoothly.

Status:

  When  the  module  is  connected  to  C-Bus  network  and  receives  valid  data  packets, 

“Status LED” flashes quickly. “Status LED” is “off” when the module doesn’t receive any data.

When the module is receiving invalid data packet ,”Status LED” will remain “on” for 5 seconds.

In some cases, when a new module is added to C-Bus network, 

“Status LED” might remain 

“on” 

for 5 seconds. This situa on must not be considered as an error.

Output LED:

  Shows the status of module’s relay.

Input LED:

 Shows the status of module’s input.

ON

1

2

3

4

5

Never set the address “0” and “1” as “0” is not valid in C-Bus protocol and “1” is always dedicated 

for 

RS-232 GatewayPro

 module. 

Check all C-Bus module addresses to avoid repev e address allocaon.

Before wiring the device, always unplug the main power.

In case of using capaciv e or inducv e loads, permissible current is less than normal mode (resisv e load) 

depending on load condion.

1

2

3

4

5

6

7 8

Color

Color Name

Pin

C-Bus

Orange/White

Orange

Green/White

Blue

Blue/White

Green

Brown/White

Brown

1

2

3

4

5

6

7

8

A(DATA+)

B(DATA-)

TXD*

RXD*

GND

GND

VCC

VCC

Use following instrucon  to connect the module to C-Bus network with Cat6 cable.

* TXD & RXD are generally applicable for modules which are working in direct mode. for this 

product TXD & RXD will be used in C-Bus networks with long cables, for GND & VCC respecv ely in 

order to lower voltage drop.

Follow the diagram below when input voltage of the Wiegand Reader is not equal to 12V DC or 

input current is higher than 100mA.