TROUBLESHOOTING
Check the following items before calling your ClimaTemp Portable spot air conditioner
reseller or a qualified technician.
CONDITION
POSSIBLE CAUSE
REMEDY
Unit does not
operate
1. Ground fault breaker trip or
breaker trip from power source.
Reset breaker or reset LCDI power cord.
2. Drain tank is full.
Empty the drain tank.
Water leaking
1. Drain port plugged
1.Clear drain outlet.
2. Drain Tank is not in the right
place.
2. Place the drain tank in the right position,
note the relative position of the float and
lever.
3. Dust and dirt particulate are
on the front filter.
3. Clean the front filter.
4. The water lever of drain tank is
too high.
4. Pull out the drain tank and empty it.
No cooling.
1. The surface of the condenser
is dirty.
1. Clean (vacuum) the surface of the
condenser. Do not use water or coil
cleaner.
2. Exhaust fan malfunction.
2. Repair, replacement of exhaust fan
motor.
3. Temperature of the external
environment is too high
3. Use the unit only if surrounding
temperature is between 64F and 113F
4.The capacitor of the
compressor is damaged.
4.Replace the capacitor
5. Input voltage is too high or
too low.
5. Make sure voltage is correct.
6. Compressor thermal overload
protection
6. Restart the unit after it has cooled down.
7. Compressor motor is
damaged.
7. Repair, replace Compressor motor if
needed.