Table 10, cont’d.: TRL Series Typical Unit Operating Pressures and Temperatures
Unit Operating Conditions, Cont’d.
015
Full Load Cooling - EAT: 80/67°F [27/19°C]
Full Load Heating - EAT: 70°F [21°C]
Airflow
(CFM)
Entering
Water
Temp F
Water
Flow
GPM
Suction
Pressure
PSIG
Super-
heat
Sub-
cooling
Water
Temp
Rise F
Air
Temp
Drop F
DB
Suction
Pressure
PSIG
Super-
heat
Sub-
cooling
Water
Temp
Rise F
Air
Temp
Drop F
DB
500
30*
2.81 126 - 136 8 - 14
8 - 10
14 - 16 19 - 25
75 - 81
9 - 12
2 - 4
1 - 2
15 - 19
3.75 114 - 124 17 - 28 14 - 18 10 - 12 20 - 26
80 - 86
9 - 13
2 - 4
4 - 4
13 - 15
4.7
114 - 124 17 - 28 13 - 18
8 - 9
20 - 26
81 - 88
10 - 13
2 - 4
3 - 3
13 - 16
40
2.81 128 - 138 8 - 13
7 - 9
14 - 16 19 - 25 92 - 100
9 - 12
2 - 4
1 - 2
17 - 21
3.75 120 - 130 14 - 23 11 - 15 10 - 12 19 - 25 95 - 103
9 - 12
2 - 4
5 - 6
16 - 20
4.7
120 - 130 14 - 23 11 - 14
8 - 9
19 - 25 97 - 105
9 - 12
2 - 4
3 - 4
16 - 20
50
2.81 131 - 141 7 - 11
8 - 10
13 - 15 18 - 24 108 - 116 8 - 10
2 - 4
2 - 2
19 - 23
3.75 126 - 136 11 - 18
9 - 13
10 - 12 18 - 24 110 - 120 9 - 12
2 - 4
5 - 7
20 - 24
4.7
126 - 136 11 - 18
9 - 12
8 - 9
18 - 24 113 - 122 9 - 12
2 - 4
4 - 5
20 - 24
60
2.81 133 - 145 7 - 11
8 - 10
13 - 15 18 - 24 122 - 132 8 - 10
2 - 4
3 - 3
21 - 25
3.75 131 - 141 8 - 14
8 - 10
9 - 11
18 - 24 124 - 134 9 - 12
2 - 4
5 - 7
22 - 26
4.7
131 - 141 8 - 14
7 - 10
7 - 8
18 - 24 126 - 137 9 - 12
2 - 4
4 - 5
22 - 27
70
2.81 135 - 147 6 - 10
9 - 12
13 - 15 17 - 23 134 - 146 8 - 10
2 - 4
4 - 4
22 - 26
3.75 135 - 147 6 - 10
7 - 9
9 - 11
17 - 23 137 - 149 9 - 12
2 - 4
6 - 8
23 - 29
4.7
135 - 147 6 - 10
7 - 9
7 - 8
17 - 23 140 - 152 9 - 12
2 - 4
5 - 6
24 - 29
80
2.81 138 - 150 6 - 10
9 - 13
12 - 14 16 - 22 146 - 158 9 - 12
2 - 4
5 - 6
23 - 28
3.75 138 - 150
5 - 9
8 - 10
9 - 11
16 - 22 149 - 161 9 - 13
2 - 4
6 - 8
23 - 29
4.7
138 - 150
5 - 9
7 - 10
7 - 8
16 - 22 152 - 164 10 - 13
2 - 4
5 - 6
24 - 29
90
2.81 140 - 152
5 - 9
11 - 15 12 - 14 16 - 22 156 - 168 9 - 13
2 - 4
5 - 7
23 - 28
3.75 141 - 153
5 - 8
9 - 12
8 - 10
16 - 22 159 - 173 10 - 14
2 - 4
7 - 9
23 - 29
4.7
141 - 153
5 - 8
8 - 11
6 - 7
16 - 22 163 - 176 11 - 14
2 - 4
6 - 7
24 - 29
100
2.81 143 - 155
5 - 9
12 - 16 11 - 13 15 - 21 164 - 178 10 - 14
2 - 4
5 - 7
23 - 28
3.75 144 - 156
5 - 8
10 - 14
8 - 10
15 - 21 170 - 184 12 - 16
2 - 4
7 - 9
22 - 26
4.7
144 - 156
5 - 8
10 - 13
6 - 7
15 - 21 173 - 188 12 - 17
2 - 4
6 - 7
22 - 27
110
2.81 145 - 157
5 - 9
14 - 18 11 - 13 14 - 20
3.75 145 - 157
5 - 9
13 - 17
8 - 8
15 - 21
4.7
145 - 157
5 - 9
12 - 17
6 - 6
15 - 21
* Based on 15% Methanol antifreeze solution.
Table 11: Water Temperature Change Through Heat Exchanger
Water Flow, gpm [l/m]
Rise, Cooling
°F, [°C]
Drop, Heating
°F, [°C]
For Closed Loop: Ground Source or
Closed Loop Systems at 3 gpm per
ton [3.2 l/m per kW]
8 - 20
[4.4 - 11.1]
3 - 18