background image

23

R e s i d e n t i a l   H & V   -   6 0 H z   H F C - 4 1 0 A

R e v. :   9   M a r c h ,   2 0 1 1 B

c l i m a t e m a s t e r. c o m

Electrical - Thermostat Wiring

Figure 24: Units With Optional ECM Fan.

Figure 25: Typical Thermostat 2 Heat/1 Cool (PSC Fan)

Thermostat Installation

The thermostat should be located on an interior wall in a 
larger room, away from supply duct drafts. DO NOT locate 
the thermostat in areas subject to sunlight, drafts or on 
external walls. The wire access hole behind the thermostat 
may in certain cases need to be sealed to prevent erroneous 
temperature measurement. Position the thermostat back 
plate against the wall so that it appears level and so the 
thermostat wires protrude through the middle of the back 
plate. Mark the position of the back plate mounting holes 
and drill holes with a 3/16” (5mm) bit. Install supplied 
anchors and secure plate to the wall. Thermostat wire must 
be 18 AWG wire. Wire the appropriate thermostat as shown 
in Figures 24 and 25 to the low voltage terminal strip on the 
CXM (units with PSC motor) or ECM control board (units 
with ECM motor).  Practically any heat pump thermostat will 
work with these units, provided it has the correct number of 
heating and cooling stages. 

ATP32U04 Thermostat

Connection to ECM Control

Compressor

Compressor Stage 2

Reversing Valve

Fan

24Vac Hot

24Vac Common

Fault LED

ECM

Board

Y1
Y2

W

DH

O
G
R
C

AL1

Y1
Y2

W

DH

O
G
R
C

L

Dehumidification

Units with CXM or DXM board and ECM fan motor, utilizing ECM dehumidification
mode (without ClimaDry option)

Notes:
1)  Units with whole house dehumidification option have slightly different

thermostat wiring.Terminal DH at the thermostat is connected to terminal H at
the DXM board

2)  ECM dehumidification mode slows down fan speed in the cooling mode when

dehumidification output from thermostat is active. Normal heating and cooling fan
speeds are not affected.

3)  ECM board DIP switch SW9 must be in dehumid. mode for

ECM dehumidification mode.

Auxiliary Heat

ATM21U01 Thermostat

Connection to CXM Control

Compressor

Heating Stage 2

Reversing Valve

Fan

24Vac Hot

24Vac Common

Fault LED

Y

Y2/W

O
G
R
C

L

Y

W

O
G
R
C

AL1

CXM

NOTICE:

 Units with ClimaDry whole house dehumidi

Ä

 cation 

option require a separate humidistat or thermostat part 
number ATP32U04 (See ClimaDry AOM for more details).

ѥ

CAUTION! 

ѥ

ѥ

CAUTION! 

ѥ

CAUTION!

 Refrigerant pressure activated water regulating 

valves should never be used with ClimateMaster 
equipment.

CAUTION!

 Many units are installed with a factory or 

¿

 eld 

supplied manual or electric shut-off valve. 

DAMAGE

WILL OCCUR

 if shut-off valve is 

closed

during unit 

operation. A high pressure switch must be installed on 
the heat pump side of any 

¿

 eld provided shut-off valves 

and connected to the heat pump controls in series with 
the built-in refrigerant circuit high pressure switch to 
disable compressor operation if water pressure exceeds 
pressure switch setting. The 

¿

 eld installed high pressure 

switch shall have a cut-out pressure of 300 psig and a 
cut-in pressure of 250 psig. This pressure switch can 
be ordered from ClimateMaster with a 1/4” internal 

À

 are 

connection as part number 39B0005N02.

Summary of Contents for Tranquility 20

Page 1: ...pen Loop Ground Water Systems 13 Water Quality Standards 15 Hot Water Generator 16 18 Electrical Line Voltage 19 20 Electrical Low Voltage Wiring 21 22 Accessory Connections 22 Electrical Thermostat W...

Page 2: ...This page was intentionally left blank...

Page 3: ...in death or serious injury DANGER labels on unit access panels must be observed WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION...

Page 4: ...units on the job site with either the original packaging or an equivalent protective covering Cap the open ends of pipes stored on the job site In areas where painting plastering and or spraying has...

Page 5: ...electrical and duct connection s If the unit is located in a confined space such as a closet provisions must be made for return air to freely enter the space by means of a louvered door etc Any acces...

Page 6: ...QHFW 3RZHU LULQJ QVXODWHG VXSSO GXFW ZLWK DW OHDVW RQH GHJ HOERZ WR UHGXFH DLU QRLVH 5HWXUQ LU 6XSSO LU 8QLW DQJHU PP WKUHDGHG URGV 8QLW 3RZHU OH LEOH XFW RQQHFWRU 2SWLRQDO RZ 3UHVVXUH URS DWHU RQWURO...

Page 7: ...Figure 4 to free top panel and discharge panel 2 Lift out the access panel and set aside Lift and rotate the discharge panel to the other position as shown being careful with the blower wiring 3 Chec...

Page 8: ...re than other units connected to the same condensate main since this may cause poor drainage for all units on the line WHEN A VENT IS INSTALLED IN THE DRAIN LINE IT MUST BE LOCATED AFTER THE TRAP IN T...

Page 9: ...be difficult to remove after the unit is installed should be removed prior to setting the unit Refer to Figures 7 and 8 for typical installation illustrations Refer to unit specifications catalog for...

Page 10: ...ows typical condensate connections Figure 10b illustrates the internal trap for a typical vertical heat pump Each unit must be installed with its own individual vent where necessary and a means to flu...

Page 11: ...uld be used when testing Do not exceed the pipe pressure rating Test entire system when all loops are assembled Flushing the Earth Loop Once piping is completed between the unit Flow Controller and th...

Page 12: ...dition the loop to a homogenous temperature This is a good time for tool cleanup piping insulation etc Then perform final flush and pressurize the loop to a static pressure of 50 75 psi 345 517 kPa wi...

Page 13: ...s than 100 ppm scaling potential is low If this method yields numbers out of range of those listed the Ryznar Stability and Langelier Saturation indecies should be calculated Use the appropriate scali...

Page 14: ...uires a flow control device mounted on the outlet of the water control valve The device is typically a brass fitting with an orifice of rubber or plastic material that is designed to allow a specified...

Page 15: ...pm Maximum Maximum Allowable at maximum water temperature Chloride Levels 10 C 24 C 38 C Copper Cupronickel 20ppm NR NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Tit...

Page 16: ...et point of the HWG is field selectable to 125 F or 150 F The 150 F set point allows more heat storage from the HWG For example consider the amount of heat that can be generated by the HWG when using...

Page 17: ...ELOW 150 F THE 150 F HWG SETPOINT MUST ONLY BE USED ON SYSTEMS THAT EMPLOY AN APPROVED ANTI SCALD VALVE PART NUMBER AVAS4 AT THE HOT WATER STORAGE TANK WITH SUCH VALVE PROPERLY SET TO CONTROL WATER TE...

Page 18: ...ng system 2 Insulate all HWG water piping with no less than 3 8 10mm wall closed cell insulation 3 Open both shut off valves and make sure the tank drain valve is closed Water Tank Refill 1 Close valv...

Page 19: ...5 0 8 18 1 20 4 25 024 12 8 60 0 1 0 40 4 0 3 9 21 1 24 3 35 0 8 21 9 25 1 35 030 13 5 61 0 1 0 40 4 0 3 9 21 8 25 2 35 0 8 22 6 26 0 35 036 14 7 72 5 1 0 40 4 0 3 9 23 0 26 7 40 0 8 23 8 27 5 40 042...

Page 20: ...ost units are shipped on the medium speed tap Consult specifications catalog for specific unit airflow tables Typical unit design delivers rated airflow at nominal static 0 15 in w g 37Pa on medium sp...

Page 21: ...tion of how water ow rate temperature is affecting the refrigeration circuit The factory setting for FP1 is for systems using water 30 F 1 1 C refrigerant temperature In low water temperature extended...

Page 22: ...can overheat the anticipator of an electromechanical thermostat Therefore only relay or triac based thermostats should be used Two stage Units Tranquility 27 TT two stage units should be designed wit...

Page 23: ...fication mode without ClimaDry option Notes 1 Units with whole house dehumidification option have slightly different thermostat wiring Terminal DH at the thermostat is connected to terminal H at the D...

Page 24: ...emergency heat mode This setting is used for residential units with internal electric heat When auxiliary electric heat is energized i e compressor and electric heat the greater of the auxiliary emerg...

Page 25: ...terface Layout 0 0RWRU RZ 9ROWDJH RQQHFWRU 6SDGH RQQHFWLRQV WR 0 RU 0 RDUG RPSUHVVRU LVFKDUJH 6HQVRU 5 RW DWHU 6HQVRU 5 2 6 6 6 6 6 6 6 6 6 2 21 6 6 6 3XPS 5HOD 0 RXQWHU IODVK SHU 0 2 5 3 6ZLWFKHV 7KH...

Page 26: ...4 1850 0 75 1 3 1300 1550 780 1020 1210 780 1400 1650 780 3 1660 0 75 1 2 1120 1330 670 870 1040 670 1200 1430 670 2 1430 0 75 1 1 940 1120 560 1010 1200 560 1 1350 064 0 75 1 4 1670 2050 1020 1300 16...

Page 27: ...1265 1078 MED 1400 1050 1332 1323 1314 1298 1282 1263 1243 1206 1169 1115 1060 LOW 1400 1050 1130 1109 1088 1086 1084 1066 1048 1052 1055 048 HI 1600 1200 1798 1781 1764 1738 1711 1688 1665 1630 1595...

Page 28: ...2 0 50 1 2 4 1290 1580 790 1010 1230 790 1290 1580 790 4 1580 3 1150 1400 700 900 1090 700 1150 1400 700 3 1400 2 1050 1280 640 820 1000 640 1020 1240 640 2 1350 1 920 1120 560 900 1080 560 1 1350 048...

Page 29: ...hould only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable provides field selection to disable the UPS feature On Enabled Off Disabled DIP switch 2...

Page 30: ...or the initial 120 seconds of a compressor run cycle FP1 is set at the factory for one try Therefore the control will go into lockout mode once the FP1 fault has occurred FP1 lockout code 4 Air coil l...

Page 31: ...2 heating 5 G Y1 Y2 W Stage 3 heating 1 Stage 3 heating 3 N A G W Emergency heat Emergency heat Emergency heat G Y or Y1 O Stage 1 cooling 2 Stage 1 cooling 4 Cooling 6 G Y1 Y2 O Stage 2 cooling 2 Sta...

Page 32: ...less than that specified above Thermostat Signals Y and W have a 1 second recognition time when being activated or being removed O and G are direct pass through signals but are monitored by the micro...

Page 33: ...these conditions on a regular basis 2 Voltage utilization range complies with AHRI Standard 110 Cooling Heating Air Limits Min ambient air DB 45 F 7 C 39 F 4 C Rated ambient air DB 80 6 F 27 C 68 F 2...

Page 34: ...stem Air in the system can cause poor operation or system corrosion Water used in the system must be potable quality initially and clean of dirt piping slag and strong chemical cleaning agents Some an...

Page 35: ...of the operating range check refrigerant pressures and compare to Tables 11 through 12 Verify correct water flow by comparing unit pressure drop across the heat exchanger versus the data in Tables 9a...

Page 36: ...8 9 0 1 7 3 3 5 7 1 3 3 1 5 2 1 1 2 9 4 8 0 9 2 6 4 4 042 5 5 8 3 11 0 1 1 2 2 3 9 0 9 2 1 3 6 0 8 2 0 3 2 0 7 1 8 3 1 048 6 0 9 0 12 0 1 3 2 6 4 5 1 1 2 5 4 2 1 0 2 3 3 8 0 9 2 2 3 5 060 7 5 11 3 15...

Page 37: ...5 20 10 15 9 14 9 14 21 9 23 9 16 1 18 1 10 3 12 3 18 24 19 25 19 25 96 106 100 110 105 115 322 342 326 346 331 351 10 15 10 15 10 15 17 22 17 22 17 22 12 2 14 2 9 3 11 3 6 4 8 4 23 29 24 30 24 30 70...

Page 38: ...3 17 19 12 6 14 6 8 4 10 4 16 22 17 23 17 23 102 112 106 116 110 120 295 315 297 317 299 319 8 13 8 13 8 13 8 13 8 13 8 13 9 1 11 1 6 9 8 9 4 7 6 7 20 26 21 27 21 27 70 1 5 2 25 3 142 152 142 152 142...

Page 39: ...20 8 22 8 15 17 9 2 11 2 17 23 18 24 18 24 96 106 100 110 105 115 300 320 304 324 309 329 10 15 10 15 10 15 9 14 9 14 9 14 10 5 12 5 7 6 9 6 4 8 6 8 21 27 22 28 22 28 70 1 5 2 25 3 132 142 131 141 131...

Page 40: ...17 22 8 13 7 12 6 11 20 2 22 2 15 2 18 2 10 2 12 2 21 27 21 27 21 27 92 102 100 110 108 118 321 341 330 350 340 360 10 15 11 16 12 17 11 16 11 16 11 16 11 6 13 6 8 9 10 9 6 8 23 29 24 30 26 32 70 1 5...

Page 41: ...14 6 11 21 23 15 6 17 6 10 2 12 2 22 28 23 29 24 30 88 98 96 106 105 115 320 340 330 350 338 358 11 17 11 17 11 17 13 18 11 16 9 14 11 7 13 7 9 11 6 8 26 32 27 33 29 35 70 1 5 2 25 3 134 144 133 143 1...

Page 42: ...clean to obtain maximum performance Filters should be inspected every month under normal operating conditions and be replaced when necessary Units should never be operated without a filter Washable hi...

Page 43: ...ng a voltmeter The fan signal is passed through the board to the external fan relay units with PSC motors only The alarm relay can either be 24VAC as shipped or dry contacts for use with DDC controls...

Page 44: ...r further help Check Main power see power problems Check fault LED code on control board Yes No No No No No Yes No Yes See HP Fault See LP LOC Fault See FP1 Fault See FP2 Fault See Condensate Fault Se...

Page 45: ...away from unit Check slope of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air filter x X Restricted...

Page 46: ...peration and air flow restrictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Check water flow Adjus...

Page 47: ...27 5 6 2 75 5 3 4 1 5HIULJHUDQW 7 SH HDW RI WUDFWLRQ EVRUSWLRQ RU HDW RI 5HMHFWLRQ ________ IORZ UDWH GLII IDFWRU BBBBBBBBBBBBB WX KU 6XSHUKHDW 6XEFRROLQJ 6XFWLRQ WHPSHUDWXUH VXFWLRQ VDWXUDWLRQ WHPS...

Page 48: ...HG SHUVRQQHO 0ROG IXQJXV RU EDFWHULD GDPDJHV RUURVLRQ RU DEUDVLRQ RI WKH SURGXFW 3URGXFWV VXSSOLHG E RWKHUV 3URGXFWV ZKLFK KDYH EHHQ RSHUDWHG LQ D PDQQHU FRQWUDU WR 0 V SULQWHG LQVWUXFWLRQV 3URGXFWV...

Page 49: ...49 Residential H V 60Hz HFC 410A Rev 9 Ma rc h 2 0 1 1 B climatemaster com Notes...

Page 50: ...Master s opinion or commendation of its products The management system governing the manufacture of ClimateMaster s products is ISO 9001 2000 certified ClimateMaster Inc 2006 97B0045N03 7300 S W 44th...

Reviews: