Page 4
To avoid equipment damage, DO NOT use these
units as a source of heating or cooling during
the construction process. The mechanical
components and filters used in these units will
quickly become clogged with construction dirt
and debris which may cause system damage.
To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit
must be serviced only by technicians who meet
local, state and federal proficiency
requirements.
All refrigerant discharged from this unit must
be recovered WITHOUT EXCEPTION.
Technicians must follow industry accepted
guidelines and all local, state and federal
statutes for the recovery and disposal of
refrigerants.
If a compressor is removed from this unit,
system refrigerant circuit oil will remain in the
compressor. To avoid leakage of compressor oil,
the refrigerant lines of the compressor must be
sealed after it is removed.
Table 1 - GT-S Physical Data
GT-S Dimensions
33
22
26
M O D E L
1 8
2 4
3 0
3 6
4 2
4 8
6 0
Compressor
Rotary
Factory Charge R22 - (oz.)
70
74
85
101
122
130
na
Water Connection Size (fpt swivel)
1-1/4" MPT (for Flow Controller)
Suction Line Sweat Connection (in.)
3/4"
3/4"
7/8"
7/8"
7/8"
7/8"
1-1/8"
Liquid Line Sweat Connection (in.)
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
1/2"
Weight - Operating
na
na
na
na
na
na
na
Weight - Packaged
na
na
na
na
na
na
na
All units have grommet compressor mounting, TXV expansion devices, 20 ga sheet metal, weather resistant cabinet,
and 7/8" & 7/8" & 1-1/8" electrical knockouts.
Hot Water Generator ready with factory installed hot gas service ports
Scroll