15
Single
Ver
tic
al A
ir D
ischar
ge C
ondensing Unit
Medium & Low Temperature – R-404A/R-507
CDV* = CDVS is Beacon II
™
† MCA = Minimum Circuit Ampacity
† † MOP = Maximum Overcurrent Protection
‡ Condensing unit data plate ratings will be based on actual system match.
Beacon II
™
and Air Defrost Units do not carry any of the evaporator fan or heater loads. Power is
brought directly to the evaporators and does not go through the condensing unit.
An evaporator heater hold out relay (option) is recommended when two or more evaporators
are connected to a single (CDV) condensing unit to allow termination on coils that have already
defrosted to prevent unnecessary steaming. This option is not needed on Beacon II
™
(CDVS)
systems wired for a Master / Slave operation. Power is brought to each Beacon evaporator. Each coil
terminates its own defrost. Refrigeration will not start until all coils have terminated defrost.
Electrical Data
Unit Model
Number
Compressor
Model
Compressor
Condenser Fan
Motors
Beacon II™ or
Air Defrost
Remote Loads
‡
RLA
LRA
Qty.
FLA
MCA
†
MOP
††
Electric Defrost
Evap.
Fan
Amps
Defrost
Heaters
Amps
System
MCA
†
System
MOP
††
208-230 Volts
CDV*150BM6
4C2067PH
48.7
294
2
9.6
70.5
110
CONTACT FACTORY FOR SYSTEM
ELECTRICAL RATINGS
CDV*200BM6
4C2397PH
57.7
352
2
14.0
86.1
125
CDV*220BM6
4B2707PH
61.5
352
2
14.0
90.9
150
CDV*250BM6
4B3139PH
75.6
436
2
14.0
108.5
175
CDV*300BM6
4B3604PH
89.7
490
3
21.0
133.1
200
CDV*330BM6
6B4060PH
100.0
550
3
21.0
146.0
225
CDV*350BM6
6B4709PH
105.1
550
3
21.0
152.4
250
CDV*400BM6
6B5406PH
141.0
700
4
28.0
204.3
325
CDV*500BM6
6B6462PH
143.6
950
4
28.0
207.5
350
CDV*130BL6
4B2707PL
43.6
294
2
9.6
64.1
100
CDV*150BL6
4B3139PL
46.2
294
2
9.6
67.4
110
CDV*200BL6
4B3604PL
57.7
352
2
9.6
81.7
125
CDV*220BL6
6B4060PL
65.4
436
2
14.0
95.8
150
CDV*250BL6
6B4709PL
69.2
436
2
14.0
100.5
150
CDV*300BL6
6B5406PL
84.6
490
2
14.0
119.8
200
CDV*400BL6
6B6462PL
97.4
700
3
21.0
142.8
225
460 Volts
CDV*150BM6
4C2067PH
24.4
147
2
4.8
35.3
60
CONTACT FACTORY FOR SYSTEM
ELECTRICAL RATINGS
CDV*200BM6
4C2397PH
28.8
176
2
7.0
43.0
70
CDV*220BM6
4B2707PH
30.8
176
2
7.0
45.5
70
CDV*250BM6
4B3139PH
37.8
218
2
7.0
54.3
90
CDV*300BM6
4B3604PH
44.9
245
3
10.5
66.6
110
CDV*330BM6
6B4060PH
50.0
275
3
10.5
73.0
110
CDV*350BM6
6B4709PH
52.6
275
3
10.5
76.3
125
CDV*400BM6
6B5406PH
70.5
350
4
14.0
102.1
150
CDV*500BM6
6B6462PH
71.8
425
4
14.0
103.8
175
CDV*130BL6
4B2707PL
21.8
147
2
4.8
32.1
50
CDV*150BL6
4B3139PL
23.1
147
2
4.8
33.7
50
CDV*200BL6
4B3604PL
28.8
176
2
4.8
40.8
70
CDV*220BL6
6B4060PL
32.7
218
2
7.0
47.9
80
CDV*250BL6
6B4709PL
34.6
218
2
7.0
50.3
80
CDV*300BL6
6B5406PL
42.3
245
2
7.0
59.9
100
CDV*400BL6
6B6462PL
48.7
350
3
10.5
71.4
110
575 Volts
CDV*150BM6
4C2067PH
19.6
117
2
4.6
29.1
40
CONTACT FACTORY FOR SYSTEM
ELECTRICAL RATINGS
CDV*200BM6
4C2397PH
23.6
140
2
5.6
35.1
50
CDV*220BM6
4B2707PH
24.4
140
2
5.6
36.1
60
CDV*250BM6
4B3139PH
30.1
165
2
5.6
43.2
70
CDV*300BM6
4B3604PH
35.9
196
3
8.4
53.3
80
CDV*330BM6
6B4060PH
39.7
220
3
8.4
58.0
90
CDV*350BM6
6B4709PH
41.7
220
3
8.4
60.5
100
CDV*400BM6
6B5406PH
56.4
280
4
11.2
81.7
125
CDV*500BM6
6B6462PH
57.1
340
4
11.2
82.6
125
CDV*130BL6
4B2707PL
17.3
117
2
4.6
26.2
40
CDV*150BL6
4B3139PL
18.6
117
2
4.6
27.9
45
CDV*200BL6
4B3604PL
23.1
140
2
4.6
33.5
50
CDV*220BL6
6B4060PL
26.9
174
2
5.6
38.5
60
CDV*250BL6
6B4709PL
27.6
174
2
5.6
40.1
60
CDV*300BL6
6B5406PL
33.3
196
2
5.6
47.2
80
CDV*400BL6
6B6462PL
39.1
280
3
8.4
57.3
90