Installation:

 

The Trade Series Ultrablade Pro LED Exit (EUBPRO-LI) is a recessed ceiling mount fitting. The EUBPRO-
LI  can  be  attached  directly  to  any  solid  surface,  or  to  a  ceiling  tile  with  the  integrated  clamping 
mechanisms. The EUBPRO-LI comes with an attached Flex and Plug. Please follow the steps below to 
install the EUBPRO-LI Exit: 

 

If replacing an Ultrablade, an Ultrablade to Ultrablade Pro adapter 2740054 (sold separately) 
is required) 

 

Create a cut-out (350mm x 48mm) in the mounting surface.  

 

Route the power cord to the mains connection and connect the 240VAC supply. 

 

Insert the EUBPRO-LI into the ceiling cavity tighten the (4) clamping screws.  

 

Alternately, fix the EUBPRO-LI to a solid surface using (4) screws through the surface material. 

 

Install the cover plate. 

 

Apply power to the fitting and test.

 

 

 

 
 
 

 

Ceiling Tile 

 

 

 

Clamping Screws 

 

            

Cover Plate 

 

Clamping Screws 

 

Solid surface screw points

 

Maintained/Non-Maintained Operating Mode: 

Press the Test Button 5 times within a 4 second period to toggle operation of the fitting between 
Maintained and Non-Maintained mode 

Changing EXIT Legend Inserts

:

  

The Ultrablade Pro Exit comes with an assortment of standard legends.  
1. 

To remove the legend, grasp the centre of the bottom trim piece and pull down slightly to 
expose the legend edge. See photo. 

2. 

Grasp the bottom edge of the legend and slide the existing legend out of the blade, while 
working the edges out along the sides. 

3. 

Slide the new legend into the blade, ensuring to fit the edges into the sides then slide the 
legend to the top of the blade. Insert one bottom corner then the other. Slide the legend down 
into the bottom trim. 

 
 
 
 
 
 

Pull the trim out and               Lift the decal and                   Insert corners (1&2)                  Insert corners (4&5), then   
the centre                                   slide out                                  then slide up (3)                         slide down             
                                    

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 hours. 
Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection 
from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are required 
to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to remain 
illuminated for the requisite time, remedial action must be taken to repair the situation and once 
completed, the unit must pass a subsequent test. For more specific information, please refer to the 
current edition of the AS 2293.3 Standard.

 

Ultrablade Maintenance: 

 

LED Lamp Replacement:

 

 

Use only the LED Strip recommended in the 
Spares Parts list of this instruction. 

 

Disconnect battery from LED driver. 

 

Remove the screw holding the driver PCA. 
Remove the PCA. 

 

Remove the 4 screws holding the battery 
bracket. Remove the bracket with the battery. 

 

Disconnect the signal cable from LED strip. 

 

Remove 4 self-tapping screws and unclip the 
LED strip. 

 

Install the new LED strip following the above 
procedure in reverse.

 

 

Battery Replacement:

 

 

Use only the battery recommended in the 
Spares List on this instruction. 

 

Remove the battery from battery 
compartment, un-plug the lead from the 
battery connector remove the old battery.  

 

Plug the new battery into the battery 
connector.  

 

Secure the battery into the battery 
compartment 

 

Trouble Shooting: 

Below are a list of common problems and their 
possible causes. 

Fault:  

The Green LED Test Switch 
indicator is not illuminated.

 

Check:  

A.C. is connected and is turned on. 

 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in 
emergency mode. 

 

Check:  

A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency 
mode, but only stays on for a short 
period. 

Check: 

Battery has been allowed to charge for 
at least 24 hours. 

 

Battery for damage. 

 

Fault:  

Green LED flashes once every 5 

          seconds-Battery is disconnected

 

Check: 

Battery is connected. 

 

Fault:  

Green LED blinks off once every 5 
seconds- Charging very flat battery

 

Allow 20min to recover battery then 
recheck 

 

Fault:  

Green LED flashes at 2Hz (Fast 
flash)- Faulty battery

 

Replace battery 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable for 

–TH 

(theatre) version (refer to spacing tables for installation positions): 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during construction. As a 
result, any Exit & Emergency Units, on these circuits, will have their batteries discharged or “cycled”. The battery in this 
fitting has been selected to give excellent long-life performance in a controlled AS2293 testing environment. Excessive 
battery cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty claims, 
as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

 

Luminaire Dimensions: 

380mm x 220mm 

Cover Plate: 

 

385mm x 67mm 

Ceiling Cut-out: 

 

350mm x 48mm  

Minimum Depth 

 

80mm 

 

 

 