Installation:
The Trade Series Ultrablade Pro LED Exit (EUBPRO-LI) is a recessed ceiling mount fitting. The EUBPRO-
LI can be attached directly to any solid surface, or to a ceiling tile with the integrated clamping
mechanisms. The EUBPRO-LI comes with an attached Flex and Plug. Please follow the steps below to
install the EUBPRO-LI Exit:
•
If replacing an Ultrablade, an Ultrablade to Ultrablade Pro adapter 2740054 (sold separately)
is required)
•
Create a cut-out (350mm x 48mm) in the mounting surface.
•
Route the power cord to the mains connection and connect the 240VAC supply.
•
Insert the EUBPRO-LI into the ceiling cavity tighten the (4) clamping screws.
•
Alternately, fix the EUBPRO-LI to a solid surface using (4) screws through the surface material.
•
Install the cover plate.
•
Apply power to the fitting and test.
Ceiling Tile
Clamping Screws
Cover Plate
Clamping Screws
Solid surface screw points
Maintained/Non-Maintained Operating Mode:
Press the Test Button 5 times within a 4 second period to toggle operation of the fitting between
Maintained and Non-Maintained mode
Changing EXIT Legend Inserts
:
The Ultrablade Pro Exit comes with an assortment of standard legends.
1.
To remove the legend, grasp the centre of the bottom trim piece and pull down slightly to
expose the legend edge. See photo.
2.
Grasp the bottom edge of the legend and slide the existing legend out of the blade, while
working the edges out along the sides.
3.
Slide the new legend into the blade, ensuring to fit the edges into the sides then slide the
legend to the top of the blade. Insert one bottom corner then the other. Slide the legend down
into the bottom trim.
Pull the trim out and Lift the decal and Insert corners (1&2) Insert corners (4&5), then
the centre slide out then slide up (3) slide down
Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 hours.
Conduct the following tests:
•
For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection
from the mains supply.
•
Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are required
to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to remain
illuminated for the requisite time, remedial action must be taken to repair the situation and once
completed, the unit must pass a subsequent test. For more specific information, please refer to the
current edition of the AS 2293.3 Standard.
Ultrablade Maintenance:
LED Lamp Replacement:
•
Use only the LED Strip recommended in the
Spares Parts list of this instruction.
•
Disconnect battery from LED driver.
•
Remove the screw holding the driver PCA.
Remove the PCA.
•
Remove the 4 screws holding the battery
bracket. Remove the bracket with the battery.
•
Disconnect the signal cable from LED strip.
•
Remove 4 self-tapping screws and unclip the
LED strip.
•
Install the new LED strip following the above
procedure in reverse.
Battery Replacement:
•
Use only the battery recommended in the
Spares List on this instruction.
•
Remove the battery from battery
compartment, un-plug the lead from the
battery connector remove the old battery.
•
Plug the new battery into the battery
connector.
•
Secure the battery into the battery
compartment
Trouble Shooting:
Below are a list of common problems and their
possible causes.
Fault:
The Green LED Test Switch
indicator is not illuminated.
Check:
A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in
emergency mode.
Check:
A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency
mode, but only stays on for a short
period.
Check:
Battery has been allowed to charge for
at least 24 hours.
Battery for damage.
Fault:
Green LED flashes once every 5
seconds-Battery is disconnected
Check:
Battery is connected.
Fault:
Green LED blinks off once every 5
seconds- Charging very flat battery
Allow 20min to recover battery then
recheck
Fault:
Green LED flashes at 2Hz (Fast
flash)- Faulty battery
Replace battery
Rated Emergency Lumen Output in accordance with AS2293.1, not applicable for
–TH
(theatre) version (refer to spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during construction. As a
result, any Exit & Emergency Units, on these circuits, will have their batteries discharged or “cycled”. The battery in this
fitting has been selected to give excellent long-life performance in a controlled AS2293 testing environment. Excessive
battery cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty claims,
as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/
Luminaire Dimensions:
380mm x 220mm
Cover Plate:
385mm x 67mm
Ceiling Cut-out:
350mm x 48mm
Minimum Depth
80mm