Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 
 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.2 Standard. 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 

Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 

 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Fault:  

Green LED flashes once every 5 seconds-Battery is disconnected

 

Check:

 

Battery is connected.

 

 

Fault:  

Green LED blinks off once every 5 seconds- Charging very flat battery

 

Allow 20min to recover battery then recheck

 

 

Fault:  

Green LED flashes at 2Hz (Fast flash)- Faulty battery

 

Replace battery

 

 

Battery Replacement 

1. 

Disconnect power. 

2. 

Remove the battery plug from the PCA 

3. 

Remove the battery mounts 

4. 

Remove the old battery 

5. 

Fit the new battery and fix in position 

6. 

Reconnect the battery to the PCA. 

 
 
 
 
 
 

Emergency Classification 

in accordance with AS2293.1 (refer to spacing tables for 

installation positions)

 

 
Please refer to the technical label on the product for classification.

 

 
 

 

 

Trade Series LED 

CIRCLITE

 Luminaire 

 

Installation & Maintenance Instruction Leaflet

 

 

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9207 0000 

Fax:

 +61 8 9207 0088 

 

New Zealand 

Phone:

 +64 800 548 448 

Designed in Australia to comply with the 
requirements of AS2293.3: 2005 and AS/NZS 
CISPR15: 2017 
 

Models:  

 

 

ECLLED-xx-xx 

ECLLED-LI

 

Economy LED Circlite 

ECLLED-LI-MS 

Economy LED Circlite with microwave movement 
sensor 

ECLLED-LI-WW 

Economy LED Circlite - Warm White 

ECLLED-LI-WW-MS 

Economy LED Circlite with microwave movement 
sensor - Warm White 

 

 
Spare Parts:

 

1560280 

Battery, Eco Lith, 3.2V 3.0Ah 

8003070 

PCA ECLLED-LI #CT10626 

 

 

 

 

 

Important:

 

It  is  illegal  for  anyone,  except  for  a  licensed  electrician  to  install  or  maintain  this  product.  Before  installation, 
ensure  that  the  electricity  supply  has  been  switched  off  and  isolated.  Installation  must  be  carried  out  in 
accordance with the relevant Australian and International Standards. 
 
 
 
 
 
 
 
 