Installation:

 

This CLIFE-PRO-SMC Surface Mount Non-Maintained Emergency Luminaire can be installed on solid 
or T-BAR ceilings or used to replace an existing unit. 

 

Locate the installation position. 

 

Refer Images and Dimensions below for the Cut-out Hole and other dimensions. 

 

Pre-drill mounting holes. 

 

Mount base plate and use suitable fixings to secure the base plate into the pilot holes. 

 

Bring in supply cables via the rear entry hole or via the end of the base plate (surface mount 
conduit entry). 

 

Terminate the supply cables to the L, N & E terminals (in the case of the 

–DALI or –DATA fittings 

terminate the DALI or DATA cable to the terminals marked Da Da or DATA). 

 

Install the top cover, containing the control gear, ensuring to reconnect the control gear assembly 
to the connector from the supply terminal block. 

 

Ensure the Battery is connected. 

 

Screw the cover to the base plate. 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 
Segment Marking on the p

roduct will include an ‘’F’’ in third segment block. 

 

For -HV fittings, screw in the supplied antenna to the antenna connector accessible on the external 
surface. 

 
Networking: 

When installing the product on a monitored network, (ZONEWORKS, HIVE, DATA, DALI) simply insert 
the relevant Smart Node PCA. 

Dimensions: 

 
 

Testing:

 

When the unit is connected to the un-switched active, it must be allowed to charge the battery for at 
least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the following tests: 

 

The emergency lamp must illuminate for at least 2 hours (4 hrs for -4HR fittings) after disconnection 
from the mains. The results of all tests are required to be recorded in a service logbook, which is to 
be kept on-site at all times. If the unit fails to illuminate for the requisite time, remedial action must 
be taken to repair the situation and once completed, the unit must pass a subsequent test.  

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

 

Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-

maintained operation). 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 
Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 
for 

–TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 