Installation:

 

The LP Argonaut Square (CWSQLEDx) can be installed either Ceiling or Wall Mounted.  

 

 

Remove the four (4) screws diffuser to the base. 

 

Remove the four (4) screws holding the gear tray to the base. 

 

Determine  the  cable  access  point.  There  are  2  locations  on  opposite  sides  of  the  fitting  for  cable 
gland/conduit entry. Entry can also be from the back of the base. Drill out the desired cable entry 
point. 

 

Drill out 4 of the mounting points in the base (see image below). 

 

Using the base as a guide, mark the 4 holes for mounting and one for mains access if using back 
cable entry.  

 

Mount the base using appropriate fixings and seal these fixings with silicone (fill any additional entry 
points with silicone also) 

 

Route the power inside the base. 

 

Connect the 240VAC (A,E,N,SA) supply to the terminal block of the gear tray. 

 

Install the gear tray to the base. 

 

Apply power to the fitting and test per the instructions. 

 

If the CTP capabilities are activated, please affix the CTP status Label to a visible surface.  

 
Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert the 
relevant Smart Node PCA. 

Dimensions: 
 
 

 
 
 

 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.3 Standard. 

 

Maintenance: 

 

Lamp Replacement:

 

 

Use only the lamp(s) recommended on the 
label inside the Argonaut.  

 

To replace the lamp bar, remove the self-
tapping screws, disconnect the signal cable 
and install the new lamp bar. 

 

Battery Replacement:

 

 

Use only the battery recommended on the 
label inside the Argonaut and on this 
instruction. 

 

Remove the fasteners holding the battery, 
un-plug the lead from the PCB and remove 
the old battery.  

 

Attach the new battery, route the DC cable 
to the PCB and plug the new battery. 

 

Trouble Shooting: 

Below are a list of common problems and their 
possible causes. 

 
Fault:  

The Green LED Test Switch 
indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in 
emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency 
mode, but only stays on for a short 
period. 

Check: 

Battery has been allowed to charge for 
at least 24 hours. 

 

Battery for damage.

 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer 
to spacing tables for installation positions):

 

C0=D50 C90=D50 
 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

 

 

 

Mounting Holes 

Cable Entry 

Reviews: