1949210
V1.3
17 October 2018
Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
The diffuser will require removal to gain access to the Test/Status Switch and LED.
Maintained fittings (CWSQLED
M
-yy-zz) cannot be scanned with a camera using the CleverSparky App
as the maintained light source interferes with the camera scanning function. To register the fitting
manually enter the serial number from the QR code and visually read the test result and enter manually
into CleverSparky.
Zoneworks and DATA Monitored Options
Argonauts Square with part numbers CWSQLEDx-ZW
, CWSQLEDx-DATA
are fitted with Zoneworks
communications modules (nodes). These fittings are monitored using either Powerline Carrier Technology
that utilises the power cable to provide data communication or a dedicated data cable to/from data routers
installed on a dedicated data trunk connected to a central Server (can also be connected via
Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, coordinate testing and
collate test data from each fitting. Zoneworks fittings can be commissioned by a single push of the test
switch or scanning of the supplied barcode. The LED Test Switch indicator provides a multifunction
indication of the status of the fitting during testing and normal operation:
State
LED Operation
Commissioned
LED on Solid (Green)
Un-commissioned
LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)
Emergency Light Test In Progress
LED flashes at 3s On (Yellow) & 0.5s Off
In the case of the DATA version a 2-
way “figure 8” cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
Argonauts Square with part numbers
CWSQLEDx-DALI
are fitted with DALI modules (nodes) that facilitate
connection and integration to 3
rd
Party Lighting Control Systems. Before installing the
CWSQLEDx-DALI
please confirm that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.
The CWSQLEDx-DALI will be addressed and configured into the control system by the Lighting Control
System Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Fitting goes into emergency mode for 10 seconds
A 2-
way “figure 8” cable and terminal block facilitates the connection to the DALI network. DALI
connections are marked as Da Da.
Argonaut Square LED Sensor Light
Installation & Maintenance Instruction Leaflet
Victoria (Head Office & Manufacturing)
195 Chesterville Rd
Moorabbin VIC 3189
Phone:
+61 3 9559 2700
Fax:
+61 3 9559 2799
New South Wales
Phone:
+61 2 8805 6400
Fax:
+61 2 8805 6444
Queensland
Phone:
+61 7 3442 9700
Fax:
+61 7 3442 9777
South Australia/Northern Territory
Phone:
+61 8 8301 8800
Fax:
+61 8 8351 8286
Western Australia
Phone:
+61 8 9248 3720
Fax:
+61 8 9248 3725
New Zealand
Phone: +64 800 548 448
Designed in Australia to comply with the requirements of
AS2293.3: 2005 and AS/NZS CISPR15: 2011
NOTE: Standard product codes with this symbol are
enabled with Clevertest Plus capability. Please refer to the
operation guide supplied with the product for details.
Models:
CWSQLEDx-yy-zz-vv
Testing:
Options:
Manual Test
zz = Blank
Non-Maintained
x = N
Zoneworks
zz = ZW
Maintained
x = M
Z/W DATA
zz = DATA
Microwave Sensor Hi/Lo Control yy = MS-HL
DALI Comp.
zz = DALI
Microwave Sensor Control
yy = MS
Clevertest
zz = CT
Black Body
vv = BLK
(NOTE: -CT Products supplied with the Clevertest Plus Symbol are activated with Clevertest
PLUS capability. Please refer to the operation guide supplied with the product for details).
Spare Parts:
1550290
BATT: LP 6.4V 3.2Ah.200mm lead.Stick.Brkt
1190320
Sensor: M/Wave Motion, SK-503L DC
(for -MS-HL)
1330120
LED Driver
– GDY250, 26W 42VDC 610mA
8002840
PCA: SQ LED Array, 215mm, 400K, 3020 LED
CCPLED-38V120C-CKIT
LED Power Pack, 38V 120mA, LP
1190325
SENSOR:M/Wave Motion, SK-601 On/Off
(for -MS)
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.