background image

1942289   

V1.3  

15 January 2021 

 

Installation:

 

 
This CFLLED Surface Mount Non-maintained Emergency can be installed on PLASTER or solid block 
walls. 
 

1. 

Take  off the front external cover  by inserting a flat blade  screwdriver into the slots along the 
bottom edge of the fitting. 

2. 

Mark the mounting hole positions on the wall and drill fixing holes  

3. 

Using the appropriate fixing hardware for the wall surface fix the CFLLED to the wall. 

4. 

If hard wiring, remove the flex and plug after removing the internal cover plate over the terminal 
block.  

5. 

If hard wiring terminates the 240V, 50Hz supply to the terminals marked A, N & E.  The cable 
entry hole through the back of the unit is shown in the image below.  Install the internal cover 
plate over the top of the terminal block. 

6. 

Re-install the External Front Cover by pushing it back into place until it clicks in top and bottom. 

7. 

If using the flex and plug, plug it into a suitable socket (240V, 50Hz). 

8. 

Adjust the LED heads into position.  Two screws are provided for each head to move them into 
position.  The front screw adjusts the L/R position (roll) and the side screw adjusts the U/D (tilt) 
position.  There is a standard positioning marker  on the  body representing a 30° roll out  and 
30° tilt down 

– this is the position that provides the maximum square area coverage when wall 

mounted at 3m  

9. 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and 
Four Segment Marking on the p

roduct will include an ‘’F’’ in third segment block. 

 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, HIVE, DATA, DALI) simply insert 
the relevant Smart Node PCA. 
 

Images and Dimensions:

 

 

 

Testing:

 

When the CFLLED unit is connected to the un-switched active, it must be allowed to charge the battery 
for  at  least  24  hours.  The  emergency  lamp  only  illuminates  during  a  power  fail.  Conduct  the  following 
tests: 
 

 

The emergency lamp must illuminate for at least  2 hours after  disconnection from the  mains.  The 
results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all 
times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the 
situation and once completed, the unit must pass a subsequent test.  

 

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

 

 

Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-
maintained operation). 

 

Below are a list of common problems and their possible causes: 

 

Fault:  

The Green LED indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected. 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 
spacing tables for installation positions):

 

 

 

N/A 

–  refer  to  the  IES  file  when  doing  computer  aided  design  or  request  spacing  guidance  from 

Clevertronics. 
 

Caution:

 

On  many  building  sites,  power  circuits  may  be  cut  off  in  an  uncontrolled  and  repetitive  basis  during 
construction.  As  a  result,  any  Lifelight  Units,  on  these  circuits,  will  have  their  batteries  discharged  or 
“cycled”. The Lithium battery in the Supalite has been selected to give excellent long-life performance in 
a  controlled  IEC  60598-2-22  testing  environment.  Excessive  battery  cycling  will  reduce  through-life 
performance and may lead to premature battery failure. Battery warranty claims, as a result of such abuse, 
are specifically EXCLUDED from Clevertronics warranty terms. 

 
Warranty:

 

 
For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

Reviews: