Refer to the supplementary operation guide supplied with the Product.

 

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 

flashing for a period up to 2 minutes. 

Note: To scan the Status LED on the luminaire, the diffuser will require removal.  

Status LED Note: 

The Status LED is High Brightness and may appear as two separate spots as 

illustrated. If Red and Green are seen at the same time, this needs to be taken 

as Yellow in the Cleverest Plus operation guide.

 

 

 

Zoneworks, HIVE and DATA Monitored Options

 

Fittings with part numbers -ZW

, -HV/-HVG, -DATA 

are fitted with Zoneworks communications modules 

(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power 

cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated 

data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can 

also be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, 

coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by 

a single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator 

provides a multifunction indication of the status of the fitting during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HV, HVG, 

DATA 

Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV, HVG 

Un-commissioned 

With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV, HVG 

Un-commissioned 

Without network connectivity 

Batt plugged-in:

 yellow 250mS, 

green 250mS, yellow 250mS, green 

250mS, green 1s 

Batt unplugged:

 red 250mS, off 

250mS, red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In 

Progress 

LED flashes at yellow 5s , 0ff 1s 

HV, HVG 

Emergency Light Test In 

Progress 

LED flashes at yellow 1s , 0ff 1s 

In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection 

to the DATA network via a multi-drop bus (daisy chain connection).  For further information of 

installation of a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning 

Guide (incl. DATA version) 

 

 

DALI EM Option

 

Luminaires with part numbers having 

-DALI 

are fitted with DALI modules (nodes) that facilitate connection 

and integration to 3

rd

 Party Lighting Control Systems.  Before installing the -DALI luminaire please confirm 

that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.  The -DALI 

luminaire  will be addressed and configured into the control system by the Lighting Control System 

Commissioning Technicians and not Clevertronics.   

State

 

LED Operation

 

Commissioned/ Un-commissioned  LED on Solid (Green) 
Emergency Light Test in progress  LED flashes at 1s On (red & green) & 1s Off 
“IDENTIFY COMMAND” 

Lamp and Status LED Flash for 30 seconds 

A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way 

“structured wiring system” lead and plug facilitating the power and DALI connection.  DALI connections 

are marked as Da Da. 

 

 

LP™ Circular Emergency Light  

 

Installation & Maintenance Instruction Leaflet

 

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9207 0000 

Fax:

 +61 8 9207 0088 

 

New Zealand 

Phone:

 +64 800 548 448 

Designed in Australia to comply with the 

requirements of AS/NZS 2293.3 2018 and AS/NZS 

CISPR15: 2017 

NOTE: Standard product codes with this symbol       are 

enabled with Clevertest Plus capability.  Please refer to 

the operation guide supplied with the product for details.

 

Models:  

 

 

CCIRC-yy-xx

 

Testing: 

 

 

 

Options:

 

 

Manual Test 

 

xx = Blank 

 

DALI Driver

 

yy = DD

 

Zoneworks

 

xx = ZW 

 

Hi/Lo Control through 

Microwave Sensor 

yy = MS-HL 

Z/W DATA  

 

xx = DATA 

 

 

DALI Registered.     

 

xx = DALI 

 

 

 

Hive

 

xx = HV/HVG    

 

 

 

Spare Parts:  

1550010

 

Replacement Battery 

8011800

 

Replacement Emergency LED 

1330091 

Replacement 240V Driver

 

AUM02870500001 

Replacement Emergency Driver  

(-HV)

 

AUM02370470001  Replacement Emergency Driver 

AUM02970150001  Replacement Emergency Driver  

(-HVG) 

 

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 

ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 

accordance with the relevant Australian and International Standards. 

 

Note: 

 

This luminaire (with reinforced insulation between control/LED terminal and AC supply) contains non-user 

replaceable light source and battery -  to be replaced (if required, refer installation instructions for 

battery/lamp replacement) by Clevertronics service personnel/agents or a registered electrician. 

 

 

 

 

 

Reviews: