background image

1947471 

V1.5  

23 June 2022 

Instruction Sheet Template - V1.3 

 Updated 20/01/2022 

Installation:

 

The L10 Weatherproof (WP) LED Exit is a 2-part assembly. The LED light source and EXIT decal is housed in a 
separate  WP  enclosure  to  the  WP  control  gear  enclosure.  The  EXIT  enclosure  is  suitable  for  temperature 
environments of -40°C to +40°C.  The remote-control gear enclosure is suitable for temperatures of 0°C to +40°C. 
The enclosure bases are attached to the wall using screws installed through the 4 isolated holes. The remote-
control gear enclosure is connected to the EXIT enclosure via a 2-core cable to be supplied by the installer (not 
supplied by Clevertronics with the product). To install the 2-part assembly follow these steps. 

Remote Control Gear: 

1. 

Remove the enclosure cover (4 plastic screws at each corner).  

2. 

Remove the gear tray (4 screws holding the gear tray onto 4 mounting posts). 

3. 

Determine power entry hole (typically the back) and separately the hole for the 2-core cable (end/side) to 
the EXIT enclosure. Drill the two holes.  

4. 

Position the box base in the mounting position.  

5. 

Mark the 4 holes for mounting. Install the base using appropriate fixings (not supplied). 

6. 

Connect the 240VAC supply to the terminal block labelled L, N, E.  

7. 

Reinstall the gear tray and reinstall the enclosure cover. 

EXIT Enclosure: 

8. 

Remove Cover Screws to remove the Enclosure Cover, Diffuser & Decal followed by the Gear Tray 

9. 

Determine the cable entry point for the 2-core cable that will come from the remote-control gear. 

10.  Drill the 2-core cable access hole in the base/end/side of the enclosure (typically the end). 
11.  Position the box base in the mounting position.  
12.  Mark the 4 holes for mounting. Install the base using appropriate fixings (not supplied). 
13.  Reinstall the Gear Tray, Enclosure Cover, Diffuser & Decal 

2 core cable connection between the 2 enclosures: 

14.  During the installation of each component the installer should consider installing the interconnecting cable 

between the two components.  This will avoid the need to re-visit each enclosure and opening the covers 
and remove the gear trays a second time.  

15.  The 2-core interconnecting cable should use a conductor size of 1.5mm

2

 to a maximum distance of 2m. 

For lengths greater than 2m, a 2.5mm

2

 conductor should be used and the cable should be fire rated to 

class WS4X up to a distance of 10m.  Please contact Clevertronics for advice on cable lengths and cable 
size beyond 10m.   

16.  Terminate the cable at each end (each enclosure) to the appropriate terminations in the images below 

marked LED+ and LED-.   

17. 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 
Segment Marking on the product will include an ‘’F’’ in third segment block.

 

18. 

(Applicable to -VENT products only

) If the enclosures are installed in a Wall Mounted fashion, please 

ensure that the Pressure Equalization Vents are facing downwards upon product installation.

 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, HIVE DATA, DALI) simply insert 
the relevant Smart Node PCA. 

Dimensions: 

 
 
 
 
 
 

Decal Replacement:

 

 
 
 
 
 
 
 
 

 

 

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.3 Standard. 

Maintenance: 

Lamp Replacement:

 

 

Use  only  the  lamp(s)  recommended  on  the  label 
inside the Weatherproof Exit.  

 

To  replace  the  lamp  bar,  remove  the  screws, 
disconnect the signal cable and install the new lamp 
bar. 

 

Battery Replacement:

 

 

Use  only  the  battery  recommended  on  the 
label  inside  the  Exit  fitting  and  on  this 
instruction. 

 

Remove the cable ties holding the battery, un-
plug the  lead  from the  PCB  and  remove  the 
old battery.  

 

Clip the new battery into the holder, route the 
DC cable to the PCB and plug the new battery 
into the PCB.  

 

Secure the battery using suitable cable ties 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 
Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 
for 

–TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

 

2-core cable termination point 

 for 

connection of the 2 enclosures

 

2-core cable 
termination point 

– 

for connection of 

4 x mounting 
ports  
Same 

240V AC 
Termination 
point L, N, 

Step 1 - Remove 
Enclosure Cover Screws

 

Step 2 - Remove the 
Diffuser from the Cover

 

Step 3 

 

Remove/Replace the 
required Decal

 

NOTE:

 

Once Decals have been replaced, repeat ‘Decal Replacement’ steps in the reverse re-install the Cover, 

Diffuser & Decal

 