Note: The fitting is designed to be installed as shown in the image below. 

 

This LWP2LIFE-PRO-WPPOD Surface mount non-maintained Emergency Luminaire can be 

installed as either ceiling mount with the PODs facing down or on the wall with the PODs rotated to 

face down. 

 

When wall mounting the fitting must be mounted 32mm off the wall to allow pods to rotate   

 

Locate the installation position. 

 

Pre-drill mounting holes per diagram below. 

 

Removed fitting cover. 

 

Use suitable fixings to fasten the fitting to the mounting surface. 

 

Taking note of the terminal block positon, drill a hole in the fitting box to suit the cable gland or 

conduit to be used for power entry.    Please ensure that the cable entry is appropriately 

sealed to maintain the IP65 rating. 

 

Terminate the supply cables to the L, N & E terminals (in the case of the –DALI or –DATA 

fittings terminate the DALI or DATA cable to the terminals marked Da Da or DATA). 

 

Ensure the Batteries and POD cables are connected. 

 

To rotate the PODs for the wall mount (WM) position loosen the internal locking nut, rotate 

and re-tighten the nut. 

 

Screw the cover to the base. 

 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert 

the relevant Smart Node PCA. 

Images and Dimensions:

 

 

 

 

 

 

 

 

 

 

 

 

Testing:

 

When the LWP2PIFE-PRO-WPPOD unit is connected to the un-switched active, it must be allowed to charge 

the battery for at least 24 hours. The emergency lamp only illuminates during a power failure. Conduct the 

following tests: 

 

During the first commissioning test the emergency lamp must illuminate for at least 2 hours after 

disconnection from the main supply. The results of all tests are required to be recorded in a service 

logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time, 

remedial action must be taken to repair the situation and once completed, the unit must pass a 

subsequent test.   

 

Press and hold Test Button in each POD or switch Off Mains Supply, check that the emergency lamp is 

On. 

 

Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off (Non-

maintained operation). 

Below are a list of common problems and their possible causes: 

 

Fault:    The Green LED indicator is not illuminated.

 

Check:    A.C. is connected and is turned on. 

 

Battery is connected. 

Test Switch for damage. 

 

Fault:    Lamp does not illuminate in emergency mode. 

 

Check:    A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:    Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 

spacing tables for installation positions):

 

 

 

Refer to the Technical Label for classification. 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any Lifelight Units, on these circuits, will have their batteries discharged or “cycled”. 

The Li-ion battery in the Lifelight has been selected to give excellent long-life performance in a controlled IEC 

60598-2-22 testing environment. Excessive battery cycling will reduce through-life performance and may lead 

to premature battery failure. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED 

from Clevertronics warranty terms. 

 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

Note: The image below shows the 
LWP2LIFE-PRO-WPPOD in the wall 
mount configuration with the PODs 
rotated down.    To mount to the ceiling 
using the same mounting instructions 
but ensure the heads are facing down. 

Note: When 
rotating the 
PODs in WM 
position ensure 
the PODs are 
level with the 
bottom of the 
main enclosure.     