Testing Procedure:

 

When the unit is connected to the un-switched active, it must be allowed to charge the battery for at 
least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the following tests: 

 

The emergency lamp must illuminate for at least 180 min after disconnection from the mains. If the 
unit fails to illuminate for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test.  

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).

 

 
Zoneworks, HIVE and DATA Monitored Options

 

Fittings  with  part  numbers  -ZW

,  -HVG,  -DATA 

are  fitted  with  Zoneworks  communications  modules 

(nodes).  These  fittings  are  monitored  using  either  Powerline  Carrier  Technology  that  utilize  the  power 
cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated 
data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also 
be  connected  via  Ethernet/Internet/Fibre).  Zoneworks  software  on  the  server  is  used  to  monitor, 
coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a 
single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides 
a multifunction indication of the status of the fitting during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HVG, DATA 

Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HVG 

Un-commissioned 
With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HVG 

Un-commissioned 
Without network connectivity 

Batt plugged-in:

 yellow 250mS, green 

250mS, yellow 250mS, green 250mS, 
green 1s 

Batt unplugged:

 red 250mS, off 

250mS, red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In Progress 

LED flashes at yellow 5s , 0ff 1s 

HVG 

Emergency Light Test In Progress 

LED flashes at yellow 1s , 0ff 1s 

 
In the case of the DATA version a 2-

way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 
version)  

 
 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 
Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. Battery for damage. 

 

 

L10

™ Freezer Cleverfit Pro LED Exit 

Installation & Maintenance Instruction Leaflet

 

 

 

 

Australia (Head Office) 

Website

www.clevertronics.com.au

 

Email: [email protected] 
Phone: +61 3 9559 2700  
Fax: +61 3 9559 2799

 

 
UK OFFICE 

Website

www.clevertronics.co.uk

 

362 Stockley Close 
West Drayton UB7 9BL 

Phone: 01895 430 255 

     

 

Models:  

 

 

LWEPRO-xx-FZR

 

Testing: 

 

 

 

 

 

Manual Test 

 

xx = Blank 

 

 

 

 

Zoneworks

 

xx = ZW 

 

 

 

 

Z/W DATA  

 

xx = DATA 

 

 

 

 

Zoneworks HIVE

 

xx = HVG

 

 

 

 

 

 

Spare Parts:

 

1530030 

Replacement Battery 

8002710 

Replacement Emergency LED Board 

8002374 

Replacement Emergency Driver 

(Manual Test)

 

8002373 

Replacement Emergency Driver 

(-ZW, -HVG)

 

 

 
Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 