background image

1943071 

V1.4  

28 June 2022 

Instruction Sheet Template - V1.3 

 Updated 20/01/2022 

Important:

 

It  is  illegal  for  anyone,  except  for  a  licensed  electrician  to  install  or  maintain  this  product.  Before  installation, 
ensure  that  the  electricity  supply  has  been  switched  off  and  isolated.  Installation  must  be  carried  out  in 
accordance with the relevant Australian and International Standards. 
 

Installation:

 

The L10 Swingblade LED Exit (LSBLED) is a surface mount (wall or ceiling) fitting. The LSBLED can be 
attached directly to any solid surface, or to a ceiling tile using the integrated mounting bracket. Please 
follow the steps below to install the LSBLED Exit: 

 

Remove the mounting bracket from the fitting. 

 

Using the bracket as a guide, mark 2 holes for mounting screws. Then install the bracket. 

 

Connect the 240VAC supply. 

 

Insert the LSBLED body into the bracket and slide to lock into position. 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 
Segment Marking on the product will incl

ude an ‘’F’’ in third segment block. 

NOTE: If product is suspended below the ceiling or mounted on a metal surface the Swingblade 
bracket cover plate accessory (S/N:2740100) is required to cover the mains terminals. 
 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert the 
relevant Smart Node PCA. 

Dimensions: 
 

Changing  Diffuser  Decals:  (Not  applicable  to  LCSBLED  and 

–TH 

options)

  

The Swingblade Exit uses Clevertronics patented “Tamper proof” Exit legend cover and comes complete with 
spare legend inserts to enable straight on, left or right arrow as well as SS/DS combinations.  
 

The tamper proof cover is held in place by 3 locking tabs recessed in the top edge of the diffuser. Use a tool to 
disengage and push the locking tabs through to release the cover and remove the insert, replacing it with the 
desired one.

 

 

To  re-install  the  clear  cover,  first  engage  the  three  small  lugs  on  the  bottom  of  the  cover  into  the  respective 
recesses in  the diffuser.  Once  you are  sure  the  lugs are  located,  carefully  push the 3  locking  tabs  back in  to 
complete the process.

  

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 hours. 
Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection 
from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are required 
to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails to remain 
illuminated for the requisite time, remedial action must be taken to repair the situation and once 
completed, the unit must pass a subsequent test. For more specific information, please refer to the 
current edition of the AS 2293.3 Standard. 
 

Swingblade Maintenance: 

Battery/Lamp Replacement:

 

 

Prise off the plastic end caps from ends using 
a terminal screwdriver 

 

Disconnect the lamp lead from the PCB and 
slide out the LED light bar.  

 

Reinsert new LED light bar, reconnect the 
lamp lead and replace the plastic end cap. 

 

Remove the central screw connecting the two 
earth leads to the earth bar. This screw holds 
the equipment tray in place.  

 

Slide the gear tray out from the test 
switch/light bar end, unplugging the AC 
connector once it is revealed.  

 

Unplug the battery lead then bend back the 
metal tabs securing the battery pack. Remove 
the battery and replace with the changeover 
battery pack. 

Re-assemble the fitting reversing the above 
procedure. It is important that the screw securing 
the two earth leads is re-installed and tightened 
correctly.

 

Trouble Shooting: 

Below are a list of common problems and their 
possible causes. 

 
Fault:  

The Green LED Test Switch 
indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in 
emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency 
mode, but only stays on for a short 
period. 

Check: 

Battery has been allowed to charge for 
at least 24 hours. 

 

Battery for damage.

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 
for 

–TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

 

Press locking tab and slide to remove from 
bracket 

Mounting Bracket 

Locking 
Tab 

Locking 
Tabs 

Reviews: