Installation:
This LLIFE-PRO Surface mount Weatherproof Emergency Luminaire can be installed on any solid or T-
BAR ceilings or used to replace an existing unit.
•
Locate the installation position for each enclosure.
•
Remove the enclosure covers.
•
Pre-drill mounting holes per diagram below.
•
Drill a hole in each enclosure to suit the cable gland or conduit to be used for LED cable entry.
•
Drill a suitable hole in the Control Gear enclosure for power entry.
•
Use suitable fixings to fasten each enclosure to the mounting surface.
•
Route the interconnecting cable between the Control Gear and the LED lamp. For distances over 2
metres, an appropriate fire rated cable must be used.
•
Connect the LED interconnect cable to the terminal block inside each enclosure. Be sure to match
the colour code between the two terminal blocks.
•
Connect the LED cable and battery to the control gear inside the control gear enclosure.
•
Connect the power to the mains.
•
Screw the covers to the enclosure bases
•
If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four
Segment Marking on the product will include an ‘’F’’ in third segment block.
•
Apply power and test the fitting.
•
(Applicable to -VENT products only)
If the products are installed in a Wall Mounted fashion,
please ensure that the Pressure Equalization Vents are facing downwards, upon product
installation.
Networking:
When installing the product on a monitored network, (ZONEWORKS, HIVE, DATA, DALI) simply insert
the relevant Smart Node PCA.
Dimensions:
Testing:
When the unit is connected to the un-switched active, it must be allowed to charge the battery for at
least 24 hours. The emergency lamp only illuminates during a power failure. Conduct the following tests:
•
During the first commissioning test the emergency lamp must illuminate for at least 2 hours after
disconnection from the main supply. The results of all tests are required to be recorded in a service
logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time,
remedial action must be taken to repair the situation and once completed, the unit must pass a
subsequent test.
•
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
•
Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1, not applicable
for
–TH (theatre) version (refer to spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.