background image

1947245   

V1.5  

10 October 2017 

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 
 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection 
from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes.  The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation and 
once completed, the unit must pass a subsequent test. For more specific information, please refer 
to the current edition of the AS 2293.3 Standard. 
 

LED Exit Maintenance: 

Lamp Replacement:

 

 

Use only the LED lamp strip recommended 
on the label inside the Exit fitting or this 
instruction. 

 

To replace the lamp, loosen the cover 
screws and remove, unplug lamp 
connector, remove nuts fastening lamp strip 
and remove, replace and reassemble. 

 

Battery Replacement:

 

 

Use only the battery recommended on the 
label inside the Exit fitting and on this 
instruction. 

 

Un-plug the lead from the Inverter pack. 
Remove the old battery and install the new 
one. 

 

Reconnect the battery cable to the inverter 
pack. 

 

Trouble Shooting: 

Below are a list of common problems and their 
possible causes. 

 
Fault:  

The Green LED Test Switch 
indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in 
emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency 
mode, but only stays on for a short 
period. 

Check: 

Battery has been allowed to charge for 
at least 24 hours. 

 

Battery for damage. 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 
spacing tables for installation positions):

 

 

 

C0=D6.3  C90=E3.2 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency  Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long life performance 
in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-life performance 
and may lead to premature battery failure. Battery warranty claims, as a result of such abuse, are 
specifically EXCLUDED from Clevertronics warranty terms. 
 
 

Warranty:

 

 
For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

L10™ Jumbo LED Exit 

Installation & Maintenance Instruction Leaflet

 

Designed in Australia to comply with the 
requirements of AS2293.3: 2005 and AS/NZS 
CISPR15: 2011. 
 

NOTE: Standard product codes with this         symbol are 
enabled with Clevertest Plus capability.  Please refer to 
the operation guide supplied with the product for details. 

Victoria (Head Office & Manufacturing) 

195 Chesterville Rd 

Moorabbin VIC 3189  

Phone: +61 3 9559 2700  

Fax: +61 3 9559 2799 

News South Wales

 

Phone: +61 2 8805 6400 

Fax:    +61 2 8805 6444 

Queensland

  

Phone:  +61 7  3442 9700 

Fax:     +61 7  3442 9777 

 

South Australia/Northern Territory

  

Phone: +61 8 8301 8800 

Fax:   +61 8 8351 8286 

 

Western Australia

  

Phone: +61 8 9248 3720 

Fax:   +61 8 9248 3725 

 

New Zealand 

Phone: +64 800 548 448

 

Models:  

 LJELED-40-xx 

Testing

 

:

 

 

 

 

 

 

 

Manual Test  

xx = Blank 

 

 

 

 

Zoneworks 

xx = ZW 

 

 

 

 

Zoneworks DATA   xx = DATA 

 

 

 

 

DALI Compatible      

xx = DALI 

 

 

 

 

Clevertest 

xx = CT 

 

 

 

 

 

 

 

(

NOTE:-CT Products supplied with the Clevertest Plus Symbol        are 

activated  with Clevertest PLUS capability. Please  refer to the operation 

guide supplied with the product for details). 

Spare Parts:  

1530010 

BATTERY:L10 3.3V 2.5AH. 200mm lead.Brkt

 

8002470 

PCA: Duris E5 Strip for LJELED.CT10050-D1 

LJELED-40-CKIT-110 

Jumbo LED Exit, Control Kit, L10

 

 
 
 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 
accordance with the relevant Australian and International Standards.

 

 

 

 

 

 

Reviews: