Clevertest and Clevertest Plus 

 

Refer to the supplementary operation guide supplied with the Product.

 

 

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 
flashing for a period up to 2 minutes. 

 

4HR:

 CTP will only test for the 2 hours (first test) and 90 minutes duration. 4 hours testing would only be 

facilitated as a Manual Discharge Test. 

 
Zoneworks, HIVE and DATA Monitored Options

 

Fittings with part numbers -ZW

, -HV, -DATA 

are fitted with Zoneworks communications modules (nodes). 

These  fittings  are  monitored  using  either  Powerline  Carrier  Technology  that  utilize  the  power  cable  to 
provide data communication, RF transceiver modules operating in the ISM band or a dedicated data cable 
to/from  data  routers  installed  on  a  dedicated  data  trunk  connected  to  a  central  Server  (can  also  be 
connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, coordinate 
testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a single push 
of  the  test  switch  or  by  scanning  the  supplied  barcode.  The  LED  Test  Switch  indicator  provides  a 
multifunction indication of the status of the fitting during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HV, DATA 

Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV 

Un-commissioned 
With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HV 

Un-commissioned 
Without network connectivity 

Batt plugged-in:

 yellow 250mS, green 

250mS, yellow 250mS, green 250mS, 
green 1s 

Batt unplugged:

 red 250mS, off 

250mS, red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In Progress 

LED flashes at yellow 5s , 0ff 1s 

HV 

Emergency Light Test In Progress 

LED flashes at yellow 1s , 0ff 1s 

In the case of the DATA version a 2-

way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 
version)  
 

DALI EM Option

 

Luminaires with part numbers having 

-DALI 

are fitted with DALI modules (nodes) that facilitate connection 

and integration to 3

rd

 Party Lighting Control Systems.  Before installing the -DALI luminaire, please confirm 

that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.  The  -DALI 
fitting  will  be  addressed  and  configured  into  the  control  system  by  the  Lighting  Control  System 
Commissioning Technicians and not Clevertronics.   

State

 

LED Operation

 

Commissioned/ Un-commissioned 

LED on Solid (Green) 

Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Lamp and Status LED Flash for 30 seconds 

 
A 2-

way “figure 8” cable and terminal block facilitates the connection to the DALI network.  DALI 

connections are marked as Da Da.  
 
 
 

 

 

L10™ LIFELIGHT PRO 

Surface Mount Spotlight Emergency 

Installation & Maintenance Instruction Leaflet

 

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9207 0000 

Fax:

 +61 8 9207 0088 

 

New Zealand 

Phone:

 +64 800 548 448 

Designed in Australia to comply with the 
requirements of AS2293.3: 2005 and AS/NZS 
CISPR15: 2017 

NOTE: Standard product codes with this symbol       are 
enabled with Clevertest Plus capability.  Please refer to 
the operation guide supplied with the product for details.

 

Models:  

 

 

LLIFE-PRO-SMS-SPOT-xx-yy

 

Testing: 

 

 

 

Options:

 

 

Manual Test 

 

xx = Blank 

 

 

4 Hour Battery 

yy = 4HR 

Zoneworks

 

xx = ZW 

 

 

 

 

Z/W DATA  

 

xx = DATA 

 

 

 

 

Zoneworks HIVE  xx = HV 

 

 

 

 

DALI Registered.     

 

xx = DALI 

 

 

 

 

Clevertest 

xx = CT   

 

 

 

 

 

(NOTE:  -CT  Products  supplied  with  the  Clevertest  Plus  Symbol                  are  activated  with 
Clevertest PLUS capability. Please refer to the operation guide supplied with the product for 
details). 

 

Spare Parts:

 

1530230 

BATT:L10 3.3V 5AH. 200mm lead, BRKT 

1100869 

Lifelight Pro Head Assembly, Ld:280mm,Rnd,LT,Gen 2 

1100872 

Lifelight Pro Head Assbly,Ld:280mm,Rnd,LT,Gen2,Blk 

AUM01370190001 

LLIFE-PRO-SMS-CKIT-NP, Lifelight Pro, Control Only, L10, OWC, NP 

 

 

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 
accordance with the relevant Australian and International Standards. 

 
 
 
 

 

 

 

 

 

 