1942300
V1.2
7 October 2022
Instruction Sheet Template - V1.5
–
Updated 09/06/2022
Installation:
This Lifelight Pro Surface Mount Spotlight Emergency can be installed on any solid surface. It comes with
an attached Flex and Plug. Please follow the steps below for installation:
•
Locate the installation position.
•
Refer Images and Dimensions below for the Cut-out Hole and other dimensions.
•
Pre-drill mounting and cable access holes.
•
Route the LED cable from the head through the surface access hole.
•
Mount the LED head using suitable fixings.
•
Connect the LED cable to the control gear pack
•
Ensure the Battery is connected.
•
Apply power to the unit and test per instructions.
•
If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four
Segment Marking on the p
roduct will include an ‘’F’’ in third segment block.
Dimensions:
Mounting Plate
Testing:
When the Lifelight Pro Surface Mount Spotlight Emergency unit is connected to the un-switched active,
it must be allowed to charge the battery for at least 24 hours. The emergency lamp only illuminates
during a power fail. Conduct the following tests:
•
The emergency lamp must illuminate for at least 2 hours after disconnection from the mains. The
results of all tests are required to be recorded in a service logbook, which is always to be kept on-
site. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the
situation and once completed, the unit must pass a subsequent test.
•
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
•
Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1, not applicable
for
–TH (theatre) version (refer to spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/
This luminaire (with reinforced insulation between control/LED terminal and AC Supply) contains non-
user replaceable light source
– to be replaced (if required) by the manufacturer or his service agent or a
similar qualified person.
Figure: Mounting Plate Dimensions