background image

1942014 

V1.2  

23 February 2021 

 

Installation:

 

The LLIFE-SM is a Non-Maintained Surface Mount (SM) fitting that can be attached directly to any solid 

surface (use appropriate fixings to suit the mounting surface). Please follow the steps below to install the 

LLIFE-SM: 

 

Remove the Lid from the Base by using a flat screwdriver to release the snap fits (see below) 

 

Cut/Drill out Cable Entry points (see image below) 

 

Drill out the required fixing holes on the Base (see image below) 

 

Mark holes on mounting surface (use drilled out holes on the Base as a template) 

 

Mount Base using appropriate fixings to ensure a secure installation (pre-drill holes if required) 

 

Insert Mains Cables through Cable Entry 

 

Terminate the Mains Cables into terminal block. Ensure Active, A & Neutral, N wires are connected 

as per Terminal Block Label. 

 

Re-attach Lid Assembly, ensuring to align Mains Connector Pins into Terminal Block 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert the 

relevant Smart Node PCA. 

Dimensions: 

 

 

Lid Removal: 

 

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 

hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 

disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 

required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 

to remain illuminated for the requisite time, remedial action must be taken to repair the situation 

and once completed, the unit must pass a subsequent test. For more specific information, please 

refer to the current edition of the AS 2293.3 Standard. 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 

Fault:   The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected 

Test Switch for damage. 

 

Fault:   Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage.

 

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 

for –TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 

discharged or “cycled”. The battery in this fitting has been selected to give excellent long life 

performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-

life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 

abuse, are specifically EXCLUDED from Clevertronics warranty terms. 