Installation:

 

The Universal Weatherproof Exit can be pole, ceiling or wall mounted. Please follow the steps below to 
install the LCWELED. 
 

PREPARATION 

 

Remove the fitting cover by loosening the (4) screws.

 

 

 

Remove the gear tray from the fitting base by the removal of the below illustrated screws. 

 

 

Locate the mounting position. 
 

CEILING MOUNT 

 

Using the fitting base, mark out the mounting points and the cable entry. 

 

Install the fitting base to the ceiling using appropriate fixings. 

 

Connect power to the gear tray and reinstall to the base. 

 

Apply power and test the fitting. 

 

Reinstall the fitting cover. 

 

WALL MOUNT 

 

Using the wall mounting adaptor, mark out the mounting points and cable entry. 

 

Attach the wall adaptor to the base. 

 

Attach the base to the wall using appropriate fixings. 

 

Connect power to the gear tray and reinstall to the base. 

 

Apply power to the fitting and test. 

 

Reinstall the fitting cover. 

 

f the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 

Segment Marking on the product will include an 

‘’F’’ in third segment block. 

 
Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, HIVE, DALI) simply insert 
the relevant Smart Node PCA. 

Dimensions: 

 
 
 
 
 
 
 

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.3 Standard. 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 
Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage.

 

 

Battery Replacement:

 

Use only the battery recommended in the Spares List on this instruction. 

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 
for 

–TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

 