Installation:
This CLIFE-PRO-SMC Surface Mount Emergency Luminaire can be installed on solid or T-BAR ceilings
or used to replace an existing unit.
•
Locate the installation position.
•
Refer Images and Dimensions below for the mounting hole dimensions.
•
Pre-drill mounting holes.
•
Mount ceiling mounting bracket and use suitable fixings to secure the bracket into the pilot holes.
•
Bring in supply cables via the top entry hole (surface mount conduit entry).
•
Terminate the supply cables to the L, N & E terminals (for -SA, terminate the Switched Live(Active)
to Lsw, for –DALI or –DATA fittings terminate the DALI or DATA cable to the terminals marked Da
Da or DATA).
•
Install Cylinder containing the control gear, ensuring to connect the supply cable to the connector
from the supply terminal block.
•
Locate and fit securing screws on sides.
•
If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four
Segment Marking on the product will include an ‘’F’’ in third segment block.
•
For -HVG fittings, screw in the supplied antenna to the antenna connector accessible on the
external surface.
•
Wall mounting bracket optional, comes with additional instructions.
•
The luminaire should be positioned so that prolonged staring into the luminaire at a distance closer
than 350mm is not expected.
Images and Dimensions:
Ceiling Mounting Bracket
Optional Wall Mounting Bracket
Luminaire Dimensions
245mm (L) x 128mm (D)
Mounting Hole Dimensions
35mm x 90mm
Mounting Hole Dimensions
70mm x 70mm
Weight
0.7kg
Weight
1.9kg
Part Number White
2740045
Part Number Black
2740048
Note:
This luminaire (with reinforced insulation between control/LED terminal and AC supply) contains non-
user replaceable light source and battery - to be replaced (if required, refer installation instructions for
battery replacement) by Clevertronics service personnel/agents or a registered electrician.
Battery Replacement:
1. Prior to any work, isolate the power to the luminaire that requires battery replacement.
2. Open the fitting by removing the securing screws on sides, support cylinder while removing screws.
3. Disconnect the Supply Connector. The Luminaire is now isolated from the Mounting Bracket.
4. Remove screws from Top Bar and the Gear Tray assembly can be removed.
5. Remove the Battery Connector from the Emergency Driver.
6. Remove the battery from the gear tray by removing mounting screws.
7. Replace battery, re-install screws and connecter to Emergency Driver.
8. Reinstall the Gear Tray, ensure the Top Bar is aligned at 90 degrees (1/4 turn) to the side securing
screw holes.
9. Reconnect the Supply Connector and fit the securing screws on sides to secure the luminaire into
the Mounting Bracket.
Testing Procedure:
When the luminaire is connected to the un-switched Live, it must be allowed to charge the battery for at
least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the following tests:
•
The emergency lamp must illuminate for at least 180 min after disconnection from the mains. The
results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all
times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the
situation and once completed, the unit must pass a subsequent test.
•
Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On.
•
Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Below are a list of common problems and their possible causes:
Fault: The Green LED indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected.
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The Li-ion battery in the Exit & Emergency Unit has been selected to give
excellent long life performance in a controlled IEC 60598-2-22 testing environment. Excessive battery
cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty
claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
https://clevertronics.co.uk/product-warranty-statement/