background image

1942295 

V1.0  

8 June 2021 

UK Instruction Sheet Template – V1.1 – Updated: 20/11/2020 

 

Zoneworks, HIVE and DATA Monitored Options

 

Fittings with part numbers -ZW,  -HVG,  -DATA are fitted with Zoneworks communications modules 

(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power 

cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated 

data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also 

be  connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, 

coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a 

single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides 

a multifunction indication of the status of the fitting during testing and normal operation: 

Option 

State 

LED Operation 

ZW, HVG, DATA  Commissioned 

LED on Solid (Green) 

ZW, DATA 

Un-commissioned 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HVG 

Un-commissioned 

With network connectivity 

Batt plugged-in:

 yellow 1s, green 1s 

Batt unplugged:

 red 1s, off 1s 

HVG 

Un-commissioned 

Without network connectivity 

Batt plugged-in:

 yellow 250mS, green 

250mS, yellow 250mS, green 250mS, 

green 1s 

Batt unplugged:

 red 250mS, off 

250mS, red 250mS,off 250mS, off 1s 

ZW, DATA 

Emergency Light Test In Progress 

LED flashes at yellow 5s , 0ff 1s 

HVG 

Emergency Light Test In Progress 

LED flashes at yellow 1s , 0ff 1s 

In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 

a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 

version) 

 

DALI EM Option

 

Luminaires with part numbers having -DALI are fitted with DALI modules (nodes) that facilitate connection 

and integration to 3rd Party Lighting Control Systems.  Before installing the -DALI fitting please confirm 

that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.  The -DALI 

fitting will be addressed and configured into the control system by the Lighting Control System 

Commissioning Technicians and not Clevertronics 

State

 

LED Operation

 

Commissioned/ Un-commissioned  LED on Solid (Green) 
Emergency Light Test in progress  LED flashes at 1s On (Yellow) & 1s Off 
“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way 

“structured wiring system” lead and plug facilitating the power and DALI connection.  DALI connections 

are marked as Da Da.  

 

Clevertest and Clevertest Plus 

Refer to the supplementary operation guide supplied with the Product. 

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 

flashing for a period up to 2 minutes.

 

 

Maintained fittings (CLIFEM-PRO-xx) cannot be scanned with a camera using the Clevertest Plus App 

as the maintained light source interferes with the camera scanning function. To register the fitting 

manually enter the serial number from the QR code and visually read the test result and enter manually 

into Clevertest Plus App.

 

 

 

 

CLP™ LIFELIGHT PRO Surface Mount 

Emergency Luminaire 

 

Installation & Maintenance Instruction Leaflet

 

 

 

 

NOTE: Standard product codes with this symbol 

are enabled with Clevertest Plus capability.  Please refer to the 

operation guide supplied with the product for details.

 

 

Australia (Head Office) 

Website: 

www.clevertronics.com.au

 

Email: [email protected] 

Phone: +61 3 9559 2700  

Fax: +61 3 9559 2799

 

 

 

IP20

 

 

 

UK OFFICE 

Website: 

www.clevertronics.co.uk

 

362 Stockley Close 

West Drayton UB7 9BL 

Phone: 01895 430 255

 

Models:  

 

 

CLIFEz

-PRO-aa-SMC-bb-xx-yy

 

Testing : 

 

 

Options:

 

 

 

Manual Test 

 

xx = Blank  

Maintained 

z = M 

 

Zoneworks

 

xx = ZW   

Non-Maintained 

z = Blank 

 

Z/W DATA  

 

xx = DATA 

Colour, Black 

yy  = BLK 

 

Zoneworks Hive

 

xx = HVG   

Warm White 

aa = WW 

 

DALI Registered      xx = DALI   

Switched Live(Active)  bb = SA 

 

 

 

 

 

 

 

 

Spare Parts:

 

1550230

 

BATT:LP 3.2V 6400mAh.200mm lead.Brkt. 

1100811 

Lifelight Pro,Head Assem,Ld:280mm,Round,Gen2,LT (Daylight White) 

1100809 

Lifelight Pro Head Ass,Ld:280mm,Rnd,Gen2,Blk,LT (Daylight White, Black) 

1100821 

Lifelight Pro,Head Assem, Ld:280mm,Rnd,WW,Gen 2 (Warm White) 

1100808 

LifelightPro,HeadAss, Ld:280mm,Rnd,WW,Gen 2,Blk (Warm White, Black) 

UKM02370030002 

CLIFE-PRO-SMS-CKIT-IC2-475, Lifelight Pro, Control Only, 475mA, LP, CTP, OWC 

 

 

 

 

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 

ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 

accordance with the relevant British Standards. 

 

 

 

 

 

 