background image

1942384 

V1.0 

25 June 2020 

 

Installation: 

 

The Circular can be installed either Ceiling or Wall Mounted.  

 

Remove the diffuser by rotating it counter-clockwise. 

 

Remove the gear-tray by loosening the 3 screws holding it in place and then slightly rotating 

the gear-tray clockwise to release it from the keyhole slots. 

 

The power cable entry to the luminaire is via the rear surface of the base through the existing 

20mm hole. Ensure appropriate cable entry provisions are made on the installation surface for 

this purpose. 

 

The base of the luminaire can be mounted to the installation surface with the use of suitable 

fasteners (Not provided). These fasteners should be placed through the mounting feet of the 

base of the luminaire. 

 

Route the power cable into the base via the existing 20mm hole at the rear of the base during 

the installation of the base. 

 

Secure the gear-tray to the base by connecting the lanyard extending from the base to the 

gear-tray. 

 

Connect the 240VAC ( ,L

SW

, L

EM

, N) supply to the terminal block of the gear tray.  

 

Secure the gear-tray to the base via the keyhole slots on the gear-tray and by tightening the 3 

screws. 

 

Fit the diffuser to the base by placing the diffuser over the base and then rotating it clockwise, 

ensuring all the slide-lock points are engaged. 

 

Apply power to the luminaire and test as per the instructions.  

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and 

update the Four Segment Marking on the product to include a ‘’F’’ in third segment block. 

Dimensions: 

Complete luminaire outer dimensions: 

327mm (Diameter) x 100mm (Max Height) 

Base Diameter: 

272mm 

 

 

 

 

 

 

 

Note: 

This luminaire (with reinforced insulation between control/LED terminal and AC supply) contains non-

user replaceable light source and battery - to be replaced (if required, refer installation instructions for 

battery replacement) by Clevertronics service personnel/agents or a registered electrician.

 

 

 

Maintenance:  

Prior to any work, 

isolate the power to the luminaire

 that requires Battery or Lamp replacement 

Battery Replacement: 

1.  Obtain access to the rear side of the gear-tray by removing the diffuser by rotating it counter-

clockwise; Then remove the gear-tray by loosening the 3 screws holding it in place and then slightly 

rotating the gear-tray clockwise to release it from the keyhole slots. 

2.  Disconnect the battery connector from the Emergency Driver. 

3.  Un-do the 2 Philips head screws to remove the battery and then replace it with the new battery, 

ensuring that the tooth-washers are re-used. 

4.  Fit the battery connector to the Emergency Driver. 

5.  Refit the gear-tray and diffuser by following the above process in reverse. 

Lamp Replacement: 

1.  Remove the diffuser by rotating it counter-clockwise to access the lamp module. If the battery 

continues to power the LED Module, then remove the gear-tray by loosening the 3 screws holding 

it in place and then slightly rotating the gear-tray clockwise to release it from the keyhole slots. 

Disconnect the battery connector from the Emergency Driver. Then refit the gear-tray to the base. 

2.  Gently push into the top of the wiring terminals and pull out the wires from the LED Module. 

3.  Un-do the 4 Philips head screws to disengage the LED module from the gear-tray. 

4.  Fit the new LED Module to the gear-tray by following the above process in reverse. Ensure the 

battery connector is refitted, if it was removed during the lamp replacement process 

Testing: 

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 

hours. Conduct the following tests: 

5.  The emergency lamp must illuminate for at least 180 min after disconnection from the mains. If the 

unit fails to illuminate for the requisite time, remedial action must be taken to repair the situation 

and once completed, the unit must pass a subsequent test.  

6.  Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

7.  Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-

maintained operation). 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

Fault:   The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected 

Test Switch for damage. 

Fault:   Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

Fault:   Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage.

 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any 

Exit & Emergency 

Units, on these circuits, will have their batteries 

discharged or “cycled”. The Li-ion battery in the luminaire has been selected to give excellent long life 

performance in a controlled IEC 60598-2-22 testing environment. Excessive battery cycling will reduce 

through-life performance and may lead to premature battery failure. Battery warranty claims, as a result 

of such abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

https://clevertronics.co.uk/product-warranty-statement/

 

 

 

Reviews: