background image

1943978 

V3.8 

19 May 2022 

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 

hours. Conduct the following tests: 

 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection 

from the mains supply. 

 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 

required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 

to remain illuminated for the requisite time, remedial action must be taken to repair the situation and 

once completed, the unit must pass a subsequent test. For more specific information, please refer to 

the current edition of the AS/NZS 2293.2 and AS/NZS 60598.2.22 Standards. 

 

 

Press and hold Test Button, the product will go into Dynamic Red mode for the initial 120 seconds 

of the test button being pressed and then switch to Dynamic Green, check that the emergency 

lamp at base is On while button is pressed. Release the Test Button, check that the emergency 

lamp at base is Off (Non-maintained operation) and the fitting returns to state prior to test. 

 

NOTE: Initiating a 1 minute Function test using the Zoneworks Software will trigger the Dynamic Red 

Mode for 60 seconds then return to normal operation.  

Initiating a Duration test using the Zoneworks Software will trigger the Dynamic Red Mode for 120 seconds 

then Dynamic Green until the Duration test is complete then return to normal operation. 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, HIVE) simply insert the 

relevant Smart Node PCA.

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

Fault:   The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected 

Test Switch for damage. 

Fault:   Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

Fault:   Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

Fault:   The Dynamic Green is not sequencing. 

Check:  The 24 Volt/VF control is connected and turned on.   

Polarity of 24V control. 

Check that the correct interface control is selected. 

Fault:   The Dynamic Red is not illuminated. 

Check:  The 24 Volt/VF control is connected and turned on.   

Polarity of 24V control. 

Check that the correct interface control is selected. 

Check that the Dynamic Red is activated on the dip switches.  

 

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 

for –TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

 

LP™ Cleverfit Pro Dynamic Red

 

Installation & Maintenance Instruction Leaflet

 

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

  

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9207 0000 

Fax:

 +61 8 9207 0088 

 

New Zealand 

Phone:

 +64 800 548 448 

Designed in Australia to comply with the requirements 

of AS2293.3:2005(when not activated in the dynamic 

green or red cross mode) and AS/NZS CISPR22: 2009 

Note: AS2293.3 Compliance not applicable to -RU and 

-RD Products 

 

Models:  

DYRC-xCP-uu-vv-ww-xx-yy-zz

 

   

Testing: 

 

 

 

Options:

 

 

Zoneworks

 

xx = ZW 

 

 

Running man

 

yy=R

 

Z/W DATA  

 

xx = DATA 

 

 

Running man with right arrow

 

yy=RR

 

Zoneworks HIVE

 

xx = HV/HVG

  

 

Running man with left arrow

 

yy=RL

 

 

 

 

 

Running man with Up arrow

 

yy=RU

 

Normally Open 

 

ww=NO 

 

 

Running man with down arrow

 

yy=RD

 

Normally Closed 

 

ww=NC

 

 

 

Dynamic Green Disabled

 

uu=DDG

 

Activated Only by Fire 

Panel

 

uu=AOFP

 

 

 

Theater Mask

 

vv=TH

 

Weatherproof 

x=W 

 

 

SoundEscape module

 

ww=SND

 

 

Spare Parts:

 

1550230

 

Replacement Battery 

8002927 

Replacement Emergency Driver

 

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 

ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 

accordance with the relevant Australian and International Standards. 

 

Clevertronics Pty Ltd is a vendor of CleverEVAC products. It is not a fire engineer or designer. It does not 

purport to recommend its products for use in any particular application or to achieve any particular outcome. 

Purchasers and users of its products must take their own steps to ensure compliance with statutory 

requirements, safe practice and suitable application of the products. 

 