Troubleshooting
5-2
750-136
Model WB Electric Boiler Manual
Low water alarm pilot light on.
•
Float-type LWCO: Water below
cutoff line on float cage.
•
Float-type LWCO: Float stuck/
switch mechanism jammed.
•
Probe-type LWCO: Probe circuit
open/water below cutoff level.
•
Probe-type LWCO: Probe or relay
faulty.
•
Assure unit has proper water
level. Check that LWCO line is at
proper level.
•
Check that float blocking plug
has been removed. Perform blow-
down of float cage. Assure switch
plate operates freely.
•
Check for loose connections/
improper wiring. Assure unit has
proper water level.
•
Replace probe or relay.
Control power pilot light on, alarm
pilot lights off, contactors not ener-
gized.
•
Alarm pilot light(s) burned out.
•
Step control fuse blown.
•
Pressure/temperature control
improperly wired to step control.
•
Replace pilot light(s).
•
Replace fuse.
•
Check that wiring is per control
literature and per unit wiring dia-
gram.
Steps do not all energize.
•
Step control faulty.
•
Contactor coil inoperative.
•
Step control relay(s) faulty.
•
Replace step control.
•
Check for loose coil connection.
Replace contactor.
•
Check that relay is tight in socket.
Replace relay.
Steps do not draw rated current
•
Branch circuit fuse(s) blown.
•
Element bussing improper.
•
Check element(s) for proper ohms
and resistance to ground then
replace fuse(s).
•
Check that element bussing is per
wiring diagram.
Contactors noisy (chatter).
•
Element(s) open.
•
Contactors damp/dirty.
•
Replace faulty element(s).
•
Blow out contactors with com-
pressed air. Remove contactor,
disassemble and clean, and
replace contactor.
Problem
Possible Cause
Action