background image

CFH Startup Guide

4

Part No. 750-293

1.2 Gas Piping

A manually operated shut-off valve and pressure regulator are provided as standard on the Model CFH boiler.
It is recommended to install an approved gas filter or strainer in the gas supply line to the boiler. Please inquire
with the local gas supply company.

The boiler shall be installed such that the gas ignition system components are protected from water (dripping,
spraying, etc.) during appliance operation and service.

If building supply gas pressure is greater than 1 psig (27.8” WC), an upstream regulator with overpressure
protection and proper gas venting will be required and must be piped to a safe point of discharge.

All gas piping and components to the boiler gas train connection must comply with NFPA 54, local codes,
and utility requirements as a minimum. Only gas approved fittings, valves, or pipe should be used. Standard
industry practice for gas piping is normally Schedule 40 black iron pipe and fittings.

See Table 1 for CFH gas pressure requirements.

1.3 Flue Gas Connection

The flue gases from the ClearFire boiler are removed via a gas-tight, temperature and corrosion resistant flue
gas pipeline. Only flue gas systems approved and tested by the relevant region or province are to be connected
to the ClearFire boiler. Refer to flue piping manufacturer for proper installation and sealing instructions.

See also Chapter 3 in the CFH Operation and Maintenance manual.

1.4 Boiler Water-Side Connections

A pressure relief valve (safety valve; 

Figure 2

), provided with the boiler,

must be installed in the mounting provided and piped to a safe point
of discharge. Use pipe sealing compound and a flat sided wrench when
securing the safety relief valve. Do not use a pipe wrench and do not
over tighten the relief valve. The safety valve must be mounted in a
vertical position so that discharge piping and code-required drains can
be  prop erly  piped to prevent  buildup of  back pressure  an d
accumulation of foreign material around the valve seat area.

Connection to the main steam header is made at the nozzle projecting
upward from the boiler shell.

Feedwater is introduced through the piping assembly installed on the
side of the boiler vessel.

Connections are provided for optional chemical feed, surface blowoff,
and overflow.

Table 1   CFH gas pressure requirements

Boiler HP

Minimum pressure required 

at gas train connection

Max. pressure

10

7.2" w.c.

28” w.c.

15

7.3" w.c.

20

7.5" w.c.

25

7.7" w.c.

30

8.5" w.c.

40

11.0" w.c.

50

10.0" w.c.

60

10.0" w.c.

Note: To measure supply pressure

at the CFH gas valve, use the
test port on the valve inlet
flange (see below). Do not
use the leak test cocks to
measure gas pressure.

Figure 2  Pressure Relief Valve

Summary of Contents for ClearFire SFH

Page 1: ...www cleaverbrooks com ClearFire Model CFH Horizontal Steam Boiler Startup Guide 750 293...

Page 2: ...essure testing of that system at test pressures in excess of 1 2 psi 3 5 kPa DANGER WARNING Should overheating occur or the gas supply valve fail to shut off do not turn off or disconnect the electric...

Page 3: ...voltage ignition transformers Control panel must be connected to earth ground For electrical wiring requirements see wiring diagram provided with the boiler or in the CFH manual Figure 1 CFH Connecti...

Page 4: ...re to be connected to the ClearFire boiler Refer to flue piping manufacturer for proper installation and sealing instructions See also Chapter 3 in the CFH Operation and Maintenance manual 1 4 Boiler...

Page 5: ...in power 115 VAC single phase 60Hz and any remote wiring should be brought to the left side of the control panel and terminated at the appropriate terminals provided Controls for the boiler feed pump...

Page 6: ...e Figure 5 include the following Combustion Air Proving Switch Low Gas Pressure Switch High Gas Pressure Switch Dual Safety Shut off Valve SSOV Depress all manual reset buttons for all controls prior...

Page 7: ...not close the vent valve until water is visible in the gauge glass The feed pump will shut off when water reaches the Pump Off probe level Check to ensure that no leaks appear at any pipe connections...

Page 8: ...pre configured with default parameter settings for the Model CFH Prior to starting the boiler verify that the factory default settings are correct for your application See the boiler operation manual...

Page 9: ...igure 12 Operation screen 2 3 4 To change the steam pressure setpoint 1 Press the yellow highlighted setpoint display window 2 Clear the current value 3 Enter the desired value 4 Press OK 1 Note Some...

Page 10: ...ble and attempt to start the burner The CB Falcon should lock out indicating Lockout 109 Ignition Failure Reconnect flame rod cable after test The CB Falcon requires a manual reset to resume operation...

Page 11: ...manual for boil out procedure 5 LOCKOUTS HOLDS AND ALERTS To assist in monitoring boiler operation the CB Falcon control system employs messages of three types Lockouts Holds and Alerts Lockouts and...

Page 12: ...Figure 15 Press this banner to access the Alert or Lockout History where a list of the most recently occurring Alerts Lockouts can be viewed To obtain more information for a particular message press t...

Page 13: ...CFH Startup Guide Part No 750 293 13 Figure 16 CFH Wiring Diagram...

Reviews: